HUD PIH Notice § 2011-29
HQS Inspections for the Housing Choice Voucher Program and Guidance Related to Electrical Outlets (HUD PIH Notices)
Operative Text
[pic] U.S. Department of Housing and
Urban Development
Public and Indian Housing
_________________________________________________________________________
Special Attention of: Notice PIH 2011-29
(HA)
Office Directors of Public Housing;
Regional Directors; Public Housing Issued:
June 3, 2011
Agencies.
Expires: Effective until
amended, superseded, or rescinded
Cross References: PIH-2010-010
_________________________________________________________________________
SUBJECT: HQS Inspections for the Housing Choice Voucher Program and
Guidance Related to Electrical Outlets
1. Purpose:
This Notice reviews the existing Housing Quality Standards (HQS)
requirements and clarifies the existing guidance that Public Housing
Agencies (PHAs) may rely upon when conducting inspections. It also
offers additional guidance on what types of three-prong electrical
outlets an inspector should consider acceptable under HQS.
2. Applicability:
This Notice applies to HUD programs that use the HQS requirements,
including the following HUD-PIH rental assistance programs: Project-
Based Voucher, Project-Based Certificate, and Housing Choice Voucher
(HCV) Programs.
3. Introduction:
The goal of HUD’s Section 8 Housing Choice Voucher (HCV) Program is to
provide “decent, safe, and sanitary” housing at an affordable cost to low-
income families. To accomplish this, HCV program regulations at 24 CFR
982.401 set forth basic housing quality standards (HQS). All units must
meet HQS both before a PHA can approve a tenancy, and throughout the term
of the lease. PHAs must inspect each assisted unit at least annually to
ensure the unit meets HQS. HQS define “standard housing” and establish
the minimum criteria for the health and safety of program participants.
Current HQS regulations consist of 13 key aspects of housing quality, and
acceptability criteria to meet each performance requirement. HQS
includes requirements for all housing types, including single and multi-
family dwelling units, as well as specific requirements for special
housing types such as manufactured homes, congregate housing, single room
occupancy, shared housing, and group residences.
4. Background:
A May 2008, HUD Office of Inspector General (OIG) report concluded that
HUD did not have adequate controls to ensure that HCV program housing was
in material compliance with HUD’s HQS. This Notice reviews the existing
HQS requirements and identifies the guidance that PHAs may rely upon when
conducting inspections until the Department issues updated guidance on
HQS.
The Notice is divided into two sections. The first section lists the HUD
program requirements that apply to HQS and supplementary guidance that
PHAs and inspectors may rely upon when conducting inspections. The
second section deals with the issue of electrical receptacles, which is
an area of concern for many inspectors conducting HQS inspections.
5. Housing Quality Standards:
A. General
The HCV program is designed to cover a diverse housing stock of different
ages, structure types, geographic location and climate. In light of this
approach, HUD issued guidance that PHAs can rely upon for the
interpretation of HQS. It is important to note that, based upon the
diversity of the housing stock nationwide, many of the criteria rely upon
the expertise and knowledge of a PHA’s housing inspectors to determine
whether a unit meets HQS. This Notice identifies program requirements
related to HQS inspections as well as reference materials that HUD has
issued to supplement the regulatory requirements.
B. Program Requirements
HUD’s current HQS regulations for the HCV program are found at 24 CFR
982.401, and consist of the 13 key aspects of housing quality and the
accompanying Performance Requirements and Acceptability Criteria. The
PHA must comply with the regulations, which are always the controlling
requirement if there is a conflict between them and any other guidance.
The Department also issued the following two inspection forms. PHAs must
comply with one of these forms when conducting HQS inspections.
1) Inspection Form HUD-52580; or
(2) Inspection Checklist, Form HUD-52580A
C. Supplemental Materials
The Department issued supplemental materials, which set out daily
operating procedures in more detail than is included in the regulations.
While the supplemental materials do not have the force of regulation,
PHAs may rely on the materials as reflective of HUD’s interpretation of
its regulations. The Department issued the following supplemental
materials to assist PHA inspectors in determining if a unit will pass the
HQS inspection:
(1) Chapter 10 of the Housing Choice Voucher Program Guidebook,
7420.10G, and
(2) Housing Inspection Manual.
Although the Department designed these materials to minimize the amount
of ambiguity and subjectivity in the application of the requirements,
there will be situations where the professional judgment of the inspector
will be necessary to differentiate between a pass or fail condition.
D. Verification of HQS Deficiency Correction
This section provides clarification regarding the need to conduct a
follow-up inspection for tenant based voucher units after a failed annual
or interim inspection.
If the PHA determined from the inspection that the unit did not meet
the HQS requirements, the PHA may allow the unit to pass upon
verification that the HQS deficiency has been corrected. The regulation
at 982.404(a)(3) states that the PHA "verifies" HQS repairs. The PHA may
elect to do a reinspection to comply with 982.404(a)(3) to verify that
all HQS deficiencies have been corrected. However, a reinspection is not
necessary if the PHA can obtain verification through other means. For
example, a PHA might accept an owner's certification that required
repairs were completed and then verify that action at the next on-site
inspection. Further, a PHA might tie the verification process to the
severity of corrections needed and/or its experience with the owner and
property. PHAs should include in the PHA’s Administrative Plan how the
PHA will verify the correction of HQS deficiencies.
In the case of initial inspections, the PHA is required to conduct a
follow-up inspection if the unit does not pass HQS pursuant to the
initial inspection. Additionally, in the case of project based vouchers,
the PHA is required to conduct follow-up inspections to determine if the
HQS deficiency is corrected pursuant to 24 CFR 983.103(e)(2).
6. Electrical Receptacles:
A. Background
The HCV program regulations at 24 CFR 982.401(f) set forth the HQS
requirements and acceptability criteria with respect to illumination and
electricity for the housing unit. The regulations state that a unit must
include the following acceptability criteria for electricity.
• the kitchen and bathroom must have one permanent ceiling or wall
light fixture in proper operating condition;
• the kitchen must have at least one electrical outlet in proper
operating condition; and
• the living room and each bedroom must have at least two electrical
outlets in proper operating condition (permanent overhead or wall-
mounted light fixtures may count as one of the required electrical
outlets).
The inspector is responsible for determining whether the outlets are in
“proper operating condition.” While the regulation does not define what
the Department considers “proper operating condition,” HUD-Form 52580A
cites examples of electrical hazards including:
• broken wiring;
• non-insulated wiring;
• frayed wiring;
• improper types of wiring, connections or insulation;
• wires lying in or located near standing water or other unsafe
places;
• light fixture hanging from electric wiring without other firm
support or fixture;
• missing cover plates on switches or outlets;
• badly cracked outlets;
• exposed fuse box connections; and
• overloaded circuits evidenced by frequently ‘’blown’’ fuses (which
the inspector determines by asking the tenant).
B. Types of Outlets and Their Proper Operating Condition
In response to an OIG audit, HUD is issuing this Notice to clarify the
proper operating condition of electrical outlets (110V/120V). There are
two basic types of outlets: two-pronged (also called “two-slotted”) and
three-pronged outlets. Three-pronged outlets have an additional hole for
a ground wire, and are “grounded outlets.” Two-pronged outlets are
“ungrounded.”
Generally, original two-pronged, ungrounded outlets and original three-
pronged, grounded outlets are acceptable under the HQS. ”Upgraded”
outlets, which have been changed from two-pronged to three-pronged, are
the major area of concern in this Notice.
[pic]
Ungrounded Outlets
Older construction (pre-1975) housing will usually have ungrounded two-
pronged outlets, which is an acceptable type of outlet under the HQS.
(Figure 1) Homes constructed with a two-wire electrical system include
only a hot and neutral wire. Two-pronged ungrounded systems and outlets
are acceptable under HQS as long as the outlet is in proper operating
condition. An owner does not need to upgrade the electrical system of
the unit (replace two-pronged outlets to three-pronged) in order for the
unit to pass an HQS inspection.
Grounded Outlets
Newer construction housing will usually have three-pronged outlets, which
are acceptable under HQS if the outlets are grounded. (Figure 2) Newer
units constructed with a three-wire electrical system include a hot,
neutral, and ground wire. This Notice outlines traditional methods of
testing grounded outlets for proper operating condition below.
“Upgraded” Outlets
Many of the cords for today’s appliances contain three-pronged plugs,
which can cause problems when an older home does not have three-pronged
outlets for these grounded plugs. In the case of older homes, owners
often replace two-pronged, ungrounded outlets with three-pronged,
grounded type outlets in order to establish appropriate outlets for
appliances that have cords with three-pronged plugs. However, in some
cases, owners may replace two-pronged, ungrounded outlets with the three-
pronged, grounded type outlets without the necessary rewiring that adds a
ground wire to the newly installed, grounded type outlet.
Three-pronged, grounded type outlets should not be substituted for
ungrounded outlets unless (1) a ground is connected to the outlet, or (2)
a Ground Fault Circuit Interrupter (GFCI) protects the outlet. (Figure 3)
Installing a new ground wire may require a licensed electrician to
install a new wire to the circuit breaker box and may be prohibitively
expensive. A more cost-effective method is to protect the outlet with a
GFCI, which provides protection to the outlet. If the GFCI senses a
difference in current flow between the hot and the neutral terminals, it
shuts off the flow of current to the outlet.
An older construction house with a grounded outlet (Figure 2) would be an
indication that the unit may have undergone some upgrading. In such
cases, the Department recommends testing a sample of outlets in the unit
to determine if three-pronged outlets are in proper operating condition,
in addition to verifying the proper operating condition of the required
number of outlets per room.
Testing of Outlets to Determine Proper Operating Condition
Two-pronged, Ungrounded Outlets
The traditional method of testing a two-pronged, ungrounded outlet is to
plug an appliance into the outlet and verify that the appliance turns on.
This simple method is acceptable for determining that the ungrounded
outlet is in proper operating condition and meets HQS.
Three-pronged Outlets
A three-pronged outlet must meet one of the following three standards for
the inspector to consider the outlet in “proper operating condition” as
required by HQS:
1. The outlet is properly grounded.
2. A GFCI protects the three-pronged, ungrounded outlet.
3. The outlet complies with the applicable state or local
building or inspection code.
The inspector needs to use an outlet tester to determine whether the
outlet is properly grounded. There are two types of outlet testers that
an inspector can use to determine a properly grounded outlet: a two-wire
tester or a three-pronged tester.
Two Wire Tester Three Prong Tester
[pic] [pic]
To test an outlet with a two-wire tester, an inspector inserts one probe
into the hot slot (usually, the smaller slot) of the outlet and one probe
into the ground hole (bottom hole). If the outlet is properly grounded,
the indicator light should light brightly in the same manner that the
light shines when the inspector inserts the probes of the tester into the
hot and neutral (right and left) slots.
To test an outlet with a three-pronged tester, the inspector should plug
the device in and note the pattern of the lights. Usually there will be
a legend printed on the device describing what the lights indicate. The
instructions provided by the manufacturer of the tester should be
followed.
If the inspector determines that the outlet is not properly grounded
based on the results of the outlet tester, he/she may need to conduct
some additional investigation to determine if a GFCI protects the outlet.
A GFCI can be located at the outlet that is being tested or upstream on
the circuit of the outlet. If the GFCI is at an outlet, it will look
similar to Figure 3 above, and the inspector should accept the outlet as
GFCI-protected after testing the functionality of the GFCI as indicated
below.
As stated above, an ungrounded outlet may be protected by a GFCI at
another outlet that is upstream from the ungrounded outlet. If the
inspector suspects that this may be the case, there is an easy way to
determine if the GFCI protects an outlet. The inspector should “trip”
all of the GFCIs in the unit; both at the outlet and in the circuit
breaker box and determine if there is power to the ungrounded outlet. If
the power to the outlet is off, then one of the GFCIs protects the
outlet.
Occasionally, a GFCI may be located on the circuit breaker at the load
center (circuit breaker box). The following image depicts a GFCI
breaker: the distinctive indicator is the “Test” button mounted on the
breaker. An inspector may want to “trip” the GFCI in order to identify
that the power shuts off to any ungrounded outlet that is protected by
the breaker. To “trip” the GFCI, the inspector would press the test
button (A) and the switch (B) will move and shut off power to the
circuit. This allows the inspector to verify that the outlet is GFCI-
protected.
[pic]
GFCI Breaker
C. Testing of Ground Fault Circuit Interrupters (GFCIs) To Determine
Proper
Operating Condition
If an outlet contains a GFCI, the GFCI must work as designed in order for
the inspector to consider the GFCI in proper operating condition.
However, a GFCI can be in proper operating condition even if it is not
grounded. A GFCI is in proper operating condition if pressing the “TEST”
button on the GFCI trips the circuit and shuts off power through the
receptacle. It is important to note that some three-prong testers have a
GFCI test button function built into the tester. The test button on a
three-prong tester only works to trip a grounded GFCI. Therefore, if the
GFCI is not grounded, the circuit tester will erroneously indicate that
the GFCI is malfunctioning. As a result, inspectors cannot depend solely
on-three prong testers to determine if a GFCI is in proper operating
condition. Instead, the inspector should press the “TEST” button, and if
the button trips the circuit and shuts off the power through the
receptacle, the GFCI is in proper operating condition.
7. For Further Information: Contact Brian Gage, Office of Housing Voucher
Management, Room 4210, Department of Housing and Urban Development, 451
7th Street, SW, Washington, DC 20410, at (202) 402-4254.
/s/
Sandra B. Henriquez, Assistant
Secretary for Public and Indian
Housing
PIH Notice § 2011-29 clarifies the Housing Quality Standards (HQS) that apply to units assisted under HUD's Housing Choice Voucher (HCV) and related programs, as governed by 24 CFR 982.401. The notice confirms that both original two-pronged ungrounded outlets and properly grounded three-pronged outlets are generally acceptable under HQS, while 'upgraded' three-pronged outlets installed without a proper ground wire or GFCI protection raise compliance concerns. It also describes how Public Housing Agencies (PHAs) may verify correction of HQS deficiencies after a failed inspection, including through means other than a full reinspection in certain tenant-based voucher situations.
Plain English — not legal advice.
Under PIH Notice § 2011-29, compliant operators of HCV-assisted units generally ensure that all required electrical outlets meet the acceptability criteria at 24 CFR 982.401(f), including having the correct number of working outlets per room. Owners who have replaced two-pronged outlets with three-pronged outlets should verify that those outlets are either properly grounded or protected by a Ground Fault Circuit Interrupter (GFCI), since ungrounded three-pronged outlets that lack GFCI protection are flagged as a concern under this notice. When a unit fails an HQS inspection, owners should be aware that the PHA's Administrative Plan will govern how deficiency corrections are verified, which may or may not require a full reinspection depending on the program type and PHA policy.
General guidance for property managers — not legal advice for your specific situation. Consult an attorney for advice on your case.
PIH Notice § 2011-29 reinforces that any unit receiving Housing Choice Voucher assistance must meet HQS — including electrical standards under 24 CFR 982.401(f) — both at the start of a tenancy and throughout the lease term. Tenants in HCV-assisted units have a right to live in housing that passes these standards, and PHAs are required to inspect assisted units at least annually. Tenants who believe their unit has unresolved HQS deficiencies, such as electrical hazards, may raise concerns with their local PHA, consult a tenant-rights organization, or explore complaint options through HUD's Office of Public and Indian Housing.
General guidance for tenants — not legal advice for your specific situation. Consult a tenant-rights organization or attorney for advice on your case.
Generated October 14, 2026 — auto-generated, not yet human-reviewed. See /transparency for methodology.
Effective Timeline
References Out
No outbound references recorded yet for this provision.
References In
No inbound references recorded yet for this provision.