Cal. Civ. Code § 110-11-1-.05

Adoption of Amendments to Codes Regarding Assisted Living Facilities and Fire Dampers

In Force
Verified 10/27/2026 · Next check 11/3/2026
effective 10/27/2026GeorgiaHabitability & Repair

Operative Text

Cal. Civ. Code § 110-11-1-.05
The following amendments to codes are hereby adopted by the
Board of Community Affairs as amendments to the Georgia State Minimum Standard
Codes for Construction:

GEORGIA AMENDMENTS TO THE 1994 STANDARD BUILDING
CODE

* Add to Section 311.2 a residential occupancy in the R2
subclassification to read as follows:

Chapter 3

Occupancy Classification

Section 311 Residential Occupancy-Group
R

311.2 Subclassifications

R2:

Assisted living facilities having residents with prompt or
slow evacuation capabilities. (NOTE: "prompt or slow evacuation capabilities"
as defined by NFPA)

* Said building code is further amended by adding an
exception to section 704.3 entitled "Tenant Fire Separation" to read as
follows:

Chapter 7

Fire Resistance Materials and Construction
Section

704 Fire Resistant Separations

704.3 Tenant Fire Separations

704.3.1

EXCEPTION:

2. In buildings housing residential assisted living
facilities with 24 hour custodial care and oversight, non-fire rated partitions
may be used to separate tenants.

and renumbering the existing Exception as number "1".

* Said building code is further amended by amending exception
1, subparagraph 3 of section 705.1.2.4 to read as follows:

Chapter 7

Fire Resistance Materials and Construction
Section

705 Protection of Openings

705.1.2 Protection of Openings in Interior Walls

705.1.2.4

subparagraph 3

1. the duct shall not exceed 100 sq. inch (0.06m2), except
when the entire building is protected by an automatic sprinkler system
complying with NFPA 13.

GEORGIA AMENDMENTS TO THE 1994 STANDARD MECHANICAL
CODE

* Amend exception 1 of subparagraph 3 of Section 610,
Paragraph 610.1.3 to read as follows:

Chapter 6

Duct Systems

Section 610 Fire Protection of Ducts

610.1 Fire Dampers

610.1.3 Exceptions

subparagraph 3.

1. the duct shall not exceed 100 sq. inch (0.06m2), except
when the entire building is protected by an automatic sprinkler system
complying with NFPA 13.
Source: Legislative text reproduced verbatim
Plain English

Ga. Comp. R. & Regs. ch. 110-11-1 § 110-11-1-.05 establishes Georgia-specific amendments to the 1994 Standard Building Code and 1994 Standard Mechanical Code, formally adopted by the Board of Community Affairs. The amendments add assisted living facilities with prompt or slow evacuation capabilities (as defined by NFPA) to the R2 residential occupancy subclassification, allow non-fire-rated partitions in assisted living buildings with 24-hour custodial care, and set a 100-square-inch duct size limit for certain fire-damper exceptions unless the entire building is covered by an NFPA 13 automatic sprinkler system. Together, these changes tailor Georgia's minimum construction and mechanical standards to the specific operational and safety characteristics of assisted living facilities.

Written by anthropic/claude-sonnet-4.6 · Reviewed on October 27, 2026

Plain English — not legal advice.

For Property Managers

Operators and developers of assisted living facilities in Georgia should be aware that § 110-11-1-.05 places such facilities in the R2 residential occupancy subclassification when residents have prompt or slow evacuation capabilities, which affects how the building must be designed and permitted. Buildings providing 24-hour custodial care and oversight may use non-fire-rated partitions between tenant spaces under the amended Section 704.3 exception, but this allowance is specific to that care level. Compliant operators also ensure that any ducts covered by the fire-damper exceptions in Sections 705.1.2.4 and 610.1.3 do not exceed 100 square inches unless the entire building is protected by an NFPA 13 sprinkler system.

General guidance for property managers — not legal advice for your specific situation. Consult an attorney for advice on your case.

For Tenants

Residents and prospective residents of assisted living facilities in Georgia may find it useful to know that § 110-11-1-.05 sets baseline construction and fire-safety standards specifically applicable to these facilities, including occupancy classification and fire-separation requirements. These standards are intended to reflect the evacuation capabilities and care needs of assisted living residents, and they form part of the minimum requirements a facility must meet to be constructed or permitted in Georgia. Individuals with concerns about whether a facility meets these construction standards may consider contacting the Georgia Board of Community Affairs or a tenant-rights organization familiar with residential care regulations.

General guidance for tenants — not legal advice for your specific situation. Consult a tenant-rights organization or attorney for advice on your case.

Generated October 27, 2026 — auto-generated, not yet human-reviewed. See /transparency for methodology.

Effective Timeline

Current
Oct 27, 2026
Click on timeline segments to view historical versions.

References Out

No outbound references recorded yet for this provision.

References In

No inbound references recorded yet for this provision.

Related Rules

§ 244.260
Compliance required
§ 14.567
ADOPTED BY REFERENCE
§ 244.340
Sewer and water connections

Source Information

Snapshot SHA:
Fetched:Oct 27, 2026, 10:01 PM UTC