Cal. Civ. Code § 110-11-1-.06

Adoption of Amendments to Codes Regarding Wood Frame Construction

In Force
Verified 10/27/2026 · Next check 11/3/2026
effective 10/27/2026GeorgiaAccessibility & Design

Operative Text

Cal. Civ. Code § 110-11-1-.06
The following amendments to codes are hereby adopted by the
Board of Community Affairs as amendments to the Georgia State Minimum Standard
Codes for Construction:

GEORGIA AMENDMENTS TO THE

1994 STANDARD BUILDING CODE

Add to Section 202, Definitions, a definition for "Shearwall
Segment" as follows:

SHEARWALL SEGMENT - a wall or portion thereof which transfers
in plane lateral shear loads to a wall or foundation below and resists
overturning.

* Said building code is further amended by adding an
"Exception 5" to Section 1606.1.1 Determination of Wind Forces, as
follows:

Exceptions:

5. Provisions of AF&PA "Wood Frame Construction Manual
for One-and-Two Family dwellings - 1995 SBC High Wind Edition" shall be
permitted for applicable wood frame buildings of Group R3 occupancy

* Said building code is further amended by adding a Section
2313 entitled "Perforated Shearwalls" as follows:

2313 Wind Provisions

2313.1 General

All buildings for which a wind analysis is required,
according to 1606.1 and which are constructed partially or wholly of wood or
wood based materials shall be designed in accordance with the provisions of
2313 and Chapter 23.

2313.2.1 Shearwall Segments

The total allowable shearwall capacity (lbs.) of each
full-height shearwall segment without openings shall be equal to the allowable
shear capacity (plf) times the length of the wall segment. Where the dead load
stabilizing moment per 1606.4 is not sufficient to prevent overturning due to
moment loads on the wall, an anchoring device with a capacity equal to the
allowable shear capacity (p11) times the wall height shall be provided at each
end of the shearwall segment. All anchoring devices shall maintain a continuous
load path to the foundation. The capacity of shearwalls with openings shall be
adjusted in accordance with 2313.2.2

2313.2.2 Openings in Shearwalls

Where openings are located within the shearwall segment, the
wall shall be entirely sheathed with structural sheathing, including areas
above and below openings. If areas above and below remain unsheathed, the
height of the unrestrained openings shall be the height of the wall. The
allowable shear capacity (p11) determined in 2313.2.1 shall be adjusted in
accordance with Table 2313.2.2 based upon the maximum opening height and the
percentage of shearwall segments containing full-height sheathing. The total
allowable shear capacity (lbs.) shall be equal to the adjusted allowable shear
capacity (plf) times the length of full-height sheathing.

Table 2313.2.2

Shear Capacity Adjustment Factors

Maximum Unrestrained Opening Height
(H)(1)

(Window or Door Height)

H/3

H/2

2H/3

5H/6

H

8' Wall

2'-8"

4'-0"

5'-4"

6'-8"

8'-0"

10' Wall

3'4"

5'-0"

6'-8"

8'-4"

10'-0"

Percent

Full-Height Effective Shear Capacity
Factors

Sheathing (2)

0%

1.00

0.67

0.50

0.40

0.33

10%

1.00

0.69

0.53

0.43

0.36

20%

1.00

0.71

0.56

0.45

0.38

30%

1.00

0.74

0.59

0.49

0.42

40%

1.00

0.77

0.63

0.53

0.45

50%

1.00

0.80

0.67

0.57

0.50

60%

1.00

0.83

0.71

0.63

0.56

70%

1.00

0.87

0.77

0.69

0.63

80%

1.00

0.91

0.83

0.77

0.71

90%

1.00

0.95

0.91

0.87

0.83

100%

1.00

1.00

1.00

1.00

1.00

1. H - the height of the tallest opening in the
shearwall.

2. The sum of the length of a shearwall that is sheathed its
full height divided by the length of the shearwall segment.

2313.2.3 Shear Capacities of Dissimilar Materials.

The allowable shear capacity of shearwall segments sheathed
on both sides, with similar or dissimilar materials, shall equal the sum of the
shear capacity of each separate side.

2313.2.4 Wood Structural Panel Diaphragm Shear
Capacities.

The allowable shear capacities in Table 23 l0.2A for
horizontal wood structural panel diaphragms shall be increased 40 percent for
wind design.

2313.2.5 Wood Structural Panel Shear Wall Capacities.

The allowable shear capacities in Table 23 l0.2B for wood
structural panel shear walls shall be increased 40 percent for wind
design.

2313.3 Wall Stud Bending Stress Increases

The fiber stress bending (Fb) design values for wood studs,
in the NDS supplement shall be increased by the factors in Table 2313.3, in
lieu of the 1.15 repetitive member factor to take into consideration the load
sharing and composite actions provided by the structural sheathing. Where the
studs are designed for bending in accordance with 1606.2.5, spaced no more than
16 inches on center, covered on the inside with a minimum of 1/2 inch gypsum
board fastened in accordance with Table 2306.1, or its equivalent, and sheathed
with a minimum of 3/8 inch structural sheathing that is attached to the studs
using a minimum of 8d common nails spaced a maximum of 6" o.c. at panel edges
and 12" o.c. in the field of the panels.

Table 2313.3

Wall Stud Bending Stress Increase Factors

Stud Size

System Factor

2x4

1.5

2x6

1.4

2x8

1.3

2x10

1.2

2x12

1.15

GEORGIA AMENDMENTS TO THE

1995 CABO ONE-AND-TWO FAMILY DWELLING
CODE

* Section 502.3 of the 155 CABO One-and-Two Family Dwelling
Code is amended to read as follows:

502.3 Allowable spans.

Joists, girders and floor sheathing shall comply with
Sections 502.3.1 through 502.3.3 and Section 503 or AF&PA "Wood Frame
Construction Manual for One-and-Two Family Dwellings - 1995 SBC High Wind
Edition."

* Said CABO Code is further amended by amending Section 602.3
to read as follows:

602.3 Exterior Walls.

Exterior walls of wood-frame construction shall be designed
and constructed in accordance with the provisions of this chapter and Figures
602.3a and 602.3b or in accordance with the provisions of AF&PA "Wood Frame
Construction Manual for One-and-Two Family Dwellings - 1995 SBC High Wind
Edition."

* Said CABO Code is further amended by amending Section 802.2
to read as follows:

802.2 Design and construction

Roof Ceilings of wood construction shall be designed and
constructed in accordance with the provisions of this chapter, or with the
"AF&PA NDS-1991 "National Design Specifications for Wood Construction", the
"CWC-1987 'Canadian Dimension Lumber Data Book", the "WWPA- 1992 Western Lumber
Span Tables for Floor and Ceiling Joists and Roof Rafters", the "Southern Pine
Maximum Spans for Joists and Rafters" or the AF&PA "Wood Frame Construction
Manual for One-and-Two Family Dwellings - 1995 SBC High Wind Edition".

* Said CABO Code is further amended by adding the following
Reference Standard to Section 4702:

Section 4702

Referenced Standards

AF&PA. Wood Frame Construction Manual for One-and-Two
Family Dwellings - 1995- SBC High Wind Edition.
Source: Legislative text reproduced verbatim
Plain English

Ga. Comp. R. & Regs. ch. 110-11-1 § 110-11-1-.06 establishes Georgia-specific amendments to the 1994 Standard Building Code and the 1995 CABO One-and-Two Family Dwelling Code, focusing on how wood-frame structures must be engineered to handle wind forces. The amendments introduce formal definitions, shearwall design requirements, capacity adjustment tables, and allowable references to the AF&PA Wood Frame Construction Manual for High Wind conditions. These rules set the technical floor for how wood-frame buildings in Georgia are designed, reviewed, and approved under the state's minimum standard construction codes.

Written by anthropic/claude-sonnet-4.6 · Reviewed on October 27, 2026

Plain English — not legal advice.

For Property Managers

Property owners and managers overseeing new construction or significant renovation of wood-frame buildings in Georgia should be aware that § 110-11-1-.06 governs how shearwalls, diaphragms, and wall studs must be engineered for wind resistance. Compliant operators typically ensure that their design professionals reference the approved standards cited in this provision—including the AF&PA Wood Frame Construction Manual for One-and-Two Family Dwellings, 1995 SBC High Wind Edition—when preparing construction documents. Permit applications for applicable Group R3 occupancy buildings and one-and-two family dwellings are generally reviewed against these amended code requirements by local building officials.

General guidance for property managers — not legal advice for your specific situation. Consult an attorney for advice on your case.

For Tenants

Tenants living in or considering renting a wood-frame home or apartment in Georgia may find it useful to know that § 110-11-1-.06 sets minimum structural standards for how such buildings must be designed to withstand wind loads. These standards are intended to ensure a baseline level of structural safety in covered buildings, and compliance is typically verified through the local building permit and inspection process. Tenants who have concerns about the structural integrity of their dwelling can contact their local building department or a tenant-rights organization to understand what inspection or complaint options may be available.

General guidance for tenants — not legal advice for your specific situation. Consult a tenant-rights organization or attorney for advice on your case.

Generated October 27, 2026 — auto-generated, not yet human-reviewed. See /transparency for methodology.

Effective Timeline

Current
Oct 27, 2026
Click on timeline segments to view historical versions.

References Out

No outbound references recorded yet for this provision.

References In

No inbound references recorded yet for this provision.

Related Rules

§ 8.54
§ 8.54 Notice.
§ 8.55
§ 8.55 Compliance information.
§ 200.937
§ 200.937 Supplementary specific procedural requirements under HUD building product standards and certification program for plastic bathtub units, plastic shower receptors and stalls, plastic lavatories, plastic water closet bowls and tanks.

Source Information

Snapshot SHA:
Fetched:Oct 27, 2026, 10:01 PM UTC