Adoption of the 2002 National Electrical Code with Georgia Amendments, the 2000 International Energy Conservation Code with Georgia Amendments and Georgia Amendments to the 2000 CABO One and Two Family Dwelling Code, 2000 Standard Building Code, 2000 Standard Plumbing Code, 2000 Standard Gas Code, Errata to the January 1, 2002 Amendments to the 2000 CABO 1 and 2 Family Dwelling Code and Errata to the January 1, 2002 Georgia Amendments to the 2000 Standard Building Code Amendments, Effective January 1, 2003

In Force
Verified 10/27/2026 · Next check 11/3/2026
effective 10/27/2026GeorgiaHabitability & Repair

Operative Text

Cal. Civ. Code § 110-11-1-.12
The Board of Community Affairs hereby adopts the following
code editions and amendments as the Georgia State Minimum Standard Codes for
Construction:

GEORGIA STATE MINIMUM STANDARD ELECTRICAL
CODE

The National Electrical Code, 2002 Edition, published by the
National Fire Protection Association, when used in conjunction with these
Georgia Amendments, shall constitute the official Georgia State Minimum
Standard Electrical Code.

Appendices

Appendices are not enforceable unless they are specifically
referenced in the body of the code or adopted for enforcement in the ordinance
of the authority having jurisdiction.

GEORGIA STATE AMENDMENTS

* Revise the National Electrical Code, 2002 Edition,
as follows:

CHAPTER 2

WIRING AND PROTECTION

ARTICLE 210

Branch Circuits

210.8 Ground-Fault Circuit-Interrupter Protection for
Personnel.

* Revise Article 210.8(B) to read as follows:

(B) Other Than Dwelling Units. All 125-volt,
single-phase, 15- and 20-ampere receptacles installed in the locations
specified in (1), (2), (3) and (4) shall have ground-fault circuit interrupter
protection for personnel.

(1) Bathrooms

(2) Rooftops

(3) Kitchens

(4) Within 6 feet of a sink or basin, excluding those listed
in Section 517.21.

Exception: Receptacles that are not readily accessible and
are supplied from a dedicated branch circuit for electric snow-melting or
deicing equipment shall be permitted to be installed in accordance with the
applicable provisions of Article 426.

ARTICLE 220 Branch-Circuit, Feeder, and
Service Calculations

III. Optional Calculations for Computing Feeder and
Service Loads

220.30 Optional Calculation - Dwelling Unit

* Delete Section 220.30(C) Heating and Air Conditioning Load
and substitute as follows:

(C) Heating and Air-Conditioning Load. The
largest of the following five selections (load in kVA) shall be included:

(1) 100 percent of the nameplate rating(s) of the air
conditioning and cooling including heat pump compressors.

(2) 100 percent of the nameplate rating(s) of electric
thermal storage and other heating systems where the usual load is expected to
be continuous at the full nameplate value. Systems qualifying under this
selection shall not be calculated under any other selection in
220.30(C).

(3) 65 percent of the nameplate rating(s) of the total
central electric space heating including heat pump compressors. If the heat
pump compressor is prevented from operating at the same time as the
supplementary heat, it does not need to be added to the supplementary heat for
the total central space heat load.

(4) 65 percent of the nameplate rating(s) of electric space
heating if less than four separately controlled units.

(5) 40 percent of the nameplate rating(s) of electric space
heating if four or more separately controlled units.

ANNEX D EXAMPLES

Example D2(c) Optional Calculation for One-Family
Dwelling with Heat Pump (Single-Phase, 240/120-Volt Service)

(see 220.30)

* Revise parts of Example D2(c) to read as follows:

15-kW Electric Heat:

5760 VA + 15,000 VA = 20,760 VA or = 20.76 Kva

20.76 kVA x 65% = 13.49 kVA

* If supplementary heat is not on at same time as heat pump,
heat pump kVA need not be added to total.

Totals

Net general load 19,280

VA Heat pump and supplementary heat 13,490 VA

Total 32,770 VA

Calculated Load for Service

32.77 kVA × 1000 + 240 V = 136.5 A

Therefore, this dwelling unit would be permitted to be served
by a 150-A service.

Members serving on the Georgia Energy Code Task Force

Jim Vaseff, AIA, Task Force Chairman

Community & Economic Development

Georgia Power Company

Morgan Wheeler, CBO, Vice

Chairman Building Official

Walton County

Mike Barcik

Director of Technical Services

The Southface Energy Institute

Jack Cantrell

Home Builders Association of Georgia

Tom J. Carty

Building Official

Peachtree City Building Department

R.A. ''Dick'' Edwards

Consultant

Leo Goebel, FMA

Facilities Manager and

CB Richard Ellis

David D. Lovich, P.E.

Manager, Codes, Standards

Technical Services

Owens Corning Corp.

Matthew Tibbs, P.E.

Advanced Engineering Solutions

Georgia Department of Community Affairs

Office of Coordinated Planning

Building Codes Section

Ted Miltiades, Manager

Wayne DuBose, Consultant

Michael Lindsey, Consultant

Bill Towson, Jr., Consultant

FOREWORD

The International Energy Conservation Code, 2000 Edition,
published by the International Codes Council and the Southern Building Code
Congress International, Inc., when used in conjunction with these Georgia
Supplements and Amendments, shall constitute the official Georgia State
Energy Code for Buildings. For high-rise and non-residential
structures, the International Energy Conservation Code adopts by reference
American Society of Heating, Refrigerating, and Air Conditioning
Engineers (ANSI/ASHRAE/IESNA) Standard 90.1-2001.

INTRODUCTION

This document supplements and amends The
International Energy Conservation Code (IECC), 2000 Edition. In cases
where there are differences between these "Supplements and Amendments" and the
IECC, or with ANSI/ASHRAE/IESNA Standard 90.1-2001, these
"Supplements and Amendments" shall take precedence.

Each Chapter of this document associates directly with the
corresponding chapter of the IECC.

* Chapter 1: Administration and Enforcement.

* Chapter 2: Definitions.

* Chapter 3: Establishes the design criteria of the entire
state of Georgia and defines the five climate zones. The climate zones
establish the design conditions for use with chapters 4, 5, 6 and 8.

* Chapter 4: Pertains to residential building design by
systems analysis, as well as the use of renewable resources such as wind,
solar, geothermal, etc. Chapter 4 has only one amendment, 402.1.3.1.4, which
establishes 0.40 as the minimum Solar Heat Gain Coefficient (SHGC) for all
Climate Zones in Georgia.

* Chapter 5: Residential compliance by designed component1
performance, thereby analyzing the total building for compliance one component
at a time. Assuming each individual component of the building meets the thermal
requirements of the code then the entire building is deemed to comply. This
chapter offers the use of "Tradeoffs" to achieve compliance by allowing the
builder to substitute or "trade-off" values between building components. A
properly executed "Georgia Trade-off Worksheet"2 or
the use of appropriate computer software such as
MECcheck3 may be used to validate
any trade-off.

* Chapter 6: Offers prescriptive compliance via the Single
Step Compliance Method by selecting an option directly from the charts in the
correct climate zone. The values from the option show the minimum requirements
for each component of a residential structure for the specific climate zone.

* Chapter 7: Pertains to building design for all commercial
buildings, except those that comply with Chapter 8, the Single Step Compliance
for Simple Commercial Buildings or appropriate computer software such as
COMcheck4 may be used to validate
compliance.

* Chapter 8: Pertains to design by acceptable practice for
commercial buildings. Where differences between this document and the IECC, or
ANSI/ASHRAE/IESNA Standard 90.1-2001 are noted, this document
shall take precedence.

* Chapter 9: Pertains to reference standards, Figure 9-1,
F2-Values for Slab-on-Grade and Figure 9-2, Group R Buildings, A-1 and A-2
Component R values/U factors.

* Appendix: Existing Appendix becomes "Appendix A" and adds a
new Appendix B with updated Prescriptive methods and Trade-off methods to
demonstrate compliance; including new Prescriptive Single Step Compliance
Tables for most commercial buildings.

SUMMARY

In summary, Chapters 4, 5 and 6 offer different methods to
achieve code compliance for low-rise residential construction and Chapters 7
and 8 offer different methods to achieve code compliance on commercial and
high-rise residential construction. Appendix B provides additional prescriptive
methods of showing compliance, some simple methods and forms to calculate and
demonstrate compliance and some illustrations to help understand the code
requirements. Individual structures should be addressed by a compliance method
from a single chapter approach and not by a combination of compliance methods.
The "basic requirements" of the IECC apply to all compliance methods.

Please note, the maximum 0.40 Solar Heat Gain
Coefficient (SHGC) and maximum 0.65 U-factor required for residential windows 5
in this document shall become effective January 1, 2004. For the period
of January 1, 2003 to December 31, 2003, the "Single Step" Residential Energy
Code Compliance packages6 may be used to determine code compliance by
disregarding the 0.40 SHGC requirement.

In dealing with the energy conservation requirements
promulgated by this code, discussion of insulation R-values and component
U-factors may appear to overshadow the matter of controlling air infiltration.
Air infiltration accounts for substantial heat loss, heat gain, and moisture
migration in a building. Proper sealing around all doors, windows, and other
envelope penetrations through the walls, ceiling and foundations is as
important to code compliance as is the installation of the proper R-value in a
component. Proper sealing shall be done by the builder and inspected by the
Building Official or Building Inspector.

It is not the intention of this code to abridge safety or
health. There may be cases where conflicts occur between this code and other
codes that are mandatory within the state. Provided safety, health, or
environmental requirements under other applicable codes are not abridged, this
code shall be enforced as written.

GEORGIA STATE AMENDMENTS

CODE REFERENCE:

Change all references from ASHRAE/IESNA 90.1-1999 to
ANSI/ ASHRAE/IESNA 90.1-2001 respectively.

APPENDICES:

Appendices are not enforceable unless they are specifically
referenced in the body of the code or adopted for enforcement in the ordinance
of the authority having jurisdiction.

1. The word "component" for purposes of this code is defined
as being a particular segment of a building such as a wall, ceiling, or floor.
Hence, the terms wall component or ceiling component.

2. See Appendix B for "Georgia Trade-Off Worksheet".

3. MECcheck is a computer program developed
by Pacific Northwest National Laboratories for the U.S. Department of Energy to
help demonstrate compliance with the IECC. Information on obtaining this
program software can be obtained by calling 800/270-CODE or by downloading free
of charge from the Internet at www.energycodes.gov.

4. COMcheck is a computer program developed
by Pacific Northwest National Laboratories for the U.S. Department of Energy to
help demonstrate compliance with the IECC. Information on obtaining this
program software can be obtained by calling 800/270-CODE or by downloading free
of charge from the Internet at
www.energycodes.gov.

5. As referenced by Chapters 5 and 6, these do not apply in a
Chapter 4 compliance analysis.

6. See Appendix B for "Single-Step" Residential Energy Code
Compliance packages.

* Revise the Georgia State Energy Code (International
Energy Conservation Code), 2000 Edition, as follows:

CHAPTER 1

ADMINISTRATION AND ENFORCEMENT

SECTION 101

SCOPE AND GENERAL REQUIREMENTS

* Delete the following sections from Chapter 1 without
substitution.

Section 101.1

Title Section 101.4.2.4 Change in occupancy

(Effective January 1, 2003)

SECTION 102

MATERIALS, SYSTEMS AND EQUIPMENT

* Revise Section 102.5.2 Fenestration product rating,
certification and labeling, 2nd paragraph to read as follows:

Section 102.5.2 Fenestration product rating,
certification and labeling.

When a manufacturer has not determined product U-factor in
accordance with NFRC 100 for a particular product line, compliance with the
building envelope requirements of this code shall be determined by assigning
and labeling such products a default U-factor in accordance with tables
102.5.2(1) and 102.5.2(2). When A SHGC or shading coefficient is used for code
compliance and a manufacturer has not determined product SHGC in accordance
with NFRC 200 for a particular product line, compliance with the building
envelope requirements of this code shall be determined by assigning and
labeling such products with a default SHGC in accordance with Table 102.5.2(3).
Product features shall be verified for the product to qualify for default value
associated with those features. Where the existence of a particular feature
cannot be determined with reasonable certainty, the product shall not receive
credit for that feature. Where a composite of materials from two different
product types is used, the product shall be assigned the higher U-factor. The
default labels shall clearly indicate:

1. The manufacturer's/assembler's name.

2. "DEFAULT VALUES"' taken from Tables
102.5.2(1), 102.5.2(2) and 102.5.2(3).

3. The manufacturer's/assembler's certification that it has
selected the appropriate default value for the product. (Effective January 1,
2003)

SECTION 104

CONSTRUCTION DOCUMENTS

* Delect Section 104 Construction documents without
substitution.

(Effective January 1, 2003)

SECTION 105

INSPECTIONS

* Delete Section 105 Inspections without substitution.

(Effective January 1, 2003)

CHAPTER 2

DEFINITIONS

SECTION 202

GENERAL DEFINITIONS

* Revise Section 202 General Definitions to read as
follows:

THERMAL CONDUCTANCE. Timed rate of heat flow
through a body (frequently per unit area) from one of its bounding surfaces to
the other for a unit temperature difference between the two surfaces, under
steady conditions (Btu/H × ft2 °F) [W/(m2 ×K)]. The insulation shall be
stabilized (aged) prior to testing for Thermal Conductance.

THERMAL RESISTANCE (R). The reciprocal of
thermal conductance (H × ft2 ×°F/Btu) [(m2 × K)/W]. All R-values shall be
stabilized (aged) R-values.

(Effective January 1, 2003)

* Revise Section 202 General Definitions to add a new
definition to read as follows:

ATTIC KNEE WALL. Any vertical or near-vertical
wall in the building envelope that has conditioned space on one side and
unconditioned attic space on the other side. If the envelope features the
insulation installed along the sloped ceiling, the vertical wall is considered
an interior wall and thus does not require insulation. (Effective January 1,
2003)

CHAPTER 3

DESIGN CONDITIONS

SECTION 301

DESIGN CRITERIA

* Delete Section 301.1 General and substitute the
following:

301.1 General. The criteria of this chapter and
Figure 302.1(11) establish the design conditions for use with Chapters 4, 5, 6
and 8.

(Effective January 1, 2003)

SECTION 302

THERMAL DESIGN PARAMETERS

* Revise Table 302.1 EXTERIOR DESIGN CONDITIONS, footnote "b"
to read as follows:

b. The degree-days heating base (HDD) (base 65° F) and
cooling base (CDD) (base 65° F) shall be Climate Zones per Figure 302.1(11).
For purposes of determining HDD, the following shall be used: Climate Zone 4B -
1999 HDD; Climate Zone 5A - 2499 HDD; Climate Zone 6B - 2999 HDD; Climate Zone
7A - 3499 HDD; and Climate 8 - 3999 HDD. Approved software that is based on
specific city or county HDD or CDD shall be acceptable to show Energy Code
compliance. (Effective January 1, 2003)

CHAPTER 4

RESIDENTIAL BUILDING DESIGN BY SYSTEMS ANALYSIS AND
DESIGN OF BUILDINGS UTILIZING RENEWABLE ENERGY SOURCES

SECTION 404

SYSTEMS ANALYSIS

* Revise Section 402.1.3.1.4 Fenestration system solar heat
gain coefficient, Standard design to read as follows:

402.1.3.1.4 Fenestration system solar heat gain
coefficient, Standard design. The fenestration system solar heat gain
coefficient (SHGC), inclusive of framed sash and glazing area, of the glazing
systems in the Standard design shall be 0.40 during periods of mechanical
heating and cooling operation. These fenestration system SHGC values shall be
multiplied together with (added in series to) the interior shading values as
specified in Section 402.1.3.1.5 to arrive at an overall solar heat gain
coefficient for the installed glazing. This requirement shall have a delayed
implementation date of January 1, 2004. (Effective January 1, 2003)

CHAPTER 5

RESIDENTIAL BUILDING DESIGN BY COMPONENT PERFORMANCE
APPROACH

SECTION 502

BUILDING ENVELOPE REQUIREMENTS

* Revise Section 502.1.3 Recessed lighting fixtures to delete
requirement No. 2 without substitution.

(Effective January 1, 2003)

* Delete Section 502.1.5 Fenestration solar heat gain
coefficient and substitute the following:

Section 502.1.5 Fenestration solar heat gain
coefficient. In all Georgia climate zones (4B through 8), the combined
solar heat gain coefficient (the area-weighted average) of all glazed
fenestration products (including the effects of any permanent exterior solar
shading devices) in the building shall not exceed 0.40. This requirement shall
have a delayed implementation date of January 1, 2004. (Effective January 1,
2003)

* Revise Table 502.2 Heating and Cooling Criteria, footnotes
"a" and "d" to read as follows:

a. Values shall be determined by using the graphs [Figures
502.2(1), 502.2(2), 502.2(3), 502.2(4), 502.2(5) and 502.2(6)] and HDD as
specified in Section 302. The minimum insulation R-values shall be: Attic knee
walls, R-19; Cavity walls, R-11; Mass walls, R-5; Roofing/ceiling, R-19; Floors
over unheated spaces, R-11; Basement walls, R-5; and Crawl space walls, R-5.
Maximum window U-factor shall be 0.65. This window requirement shall have a
delayed implementation date of January 1, 2004.

d. Slab edge insulation shall not be used for unheated slabs
in Georgia. (Effective January 1, 2003)

* Delete Section 502.2.4 Compliance by prescriptive
specification on an individual component basis and substitute the
following:

Section 502.2.4 Compliance by prescriptive
specification on an individual component basis. For buildings with
fenestration less than or equal to 15 percent, 18 percent, 25 percent, or 30
percent (Type A-1 residential buildings) or 25 percent (Type A-2 residential
buildings) of the gross exterior wall area, the thermal resistance of
insulation applied to the opaque building envelope components shall be greater
than or equal to the minimum R-values, and the thermal transmittance of all
fenestration assemblies shall be less than or equal to the maximum U-factors
shown in Tables 502.2.4(1), 502.2.4(2), 502.2.4(3), 502.2.4(4) or 502.2.4(5) as
applicable. Sections 502.2.4.1 through 502.2.4.12 and 502.2.4.15 through
502.2.4.17 shall apply to the use of these tables.

(Effective January 1, 2003)

* Delete Tables 502.2.4(1) through 502.2.4(9) in their
entirety and substitute the following:

(Effective January 1, 2003)

* Delete Section 502.2.4.4 Window area, exempt and substitute
the following:

502.2.4.4 Window area exempt. Five (5) percent
of the total window area computed under Section 502.2.4.3 shall be exempt from
the "Glazing U-factor" and Solar Heat Gain Coefficient (SHGC)
requirements.

(Effective January 1, 2003)

* Delete Sections 502.2.4.13 and 502.2.4.14 without
substitution.

(Effective January 1, 2003)

* Delete Section 502.2.4.15 Fenestration solar heat gain
coefficient and substitute the following:

502.2.4.15 Fenestration solar heat gain coefficient.
In all Georgia climate zones (4B through 8), fenestration products shall
also meet the requirements of Section 502.1.5. This window requirement shall
have a delayed implementation date of January 1, 2004. (Effective January 1,
2003)

* Revise Section 502.2.5 Prescriptive path for additions and
window replacements to read as follows:

502.2.5 Prescriptive path for additions and window
replacements. As an alternative to demonstrating compliance with Section
402 and 502.2, additions with a conditioned floor area less than 500 square
feet (46.5 m2) to existing single-family residential
buildings and structures shall meet the prescriptive envelope component
criteria in Table 502.2.5 for the designated Climate Zones applicable to the
location. The U-factor of each individual fenestratiion product (windows, doors
and skylights) shall be used to calculate an areaweighted average fenestration
product U-factor for the addition, which shall not exceed the applicable listed
values in Table 502.2.5. For additions, the total area of fenestration products
shall not exceed 40 percent of the gross wall and roof area of the addition.
The R-values for opaque thermal envelope components shall be equal to or
greater than the applicable listed values in Table 502.2.5. Replacement
fenestration products (where the entire unit, including the frame, sash and
glazing, is replaced) shall meet the prescriptive fenestration U-factor
criteria in Table 502.2.5 for the designated Climate Zones applicable to the
location. Fenestration products used in additions and as replacement windows in
accordance with this section shall also meet the requirements of Section
502.1.5 in all Georgia climate zones (4B through 8).

Remaining exception unchanged.

(Effective January 1, 2003)

* Delete Table 502.2.5 in its entirety and substitute the
following:

(Effective January 1, 2003)

CHAPTER 6

SIMPLIFIED PRESCRIPTIVE REQUIREMENTS FOR RESIDENTIAL
BUILDINGS, TYPE A-1 AND A-2

SECTION 601

GENERAL

* Revise Section 601.2.1 Residential Buildings, Type A-1 to
read as follows:

601.2.1 Residential Buildings, Type A-1.
Compliance for Type A-1 residential buildings shall be demonstrated by either:

1. Meeting the requirements of this chapter for buildings
with a fenestration area that does not exceed 18 percent of the gross area of
exterior walls; or

2. Meeting the requirements of Chapter 4, or Chapter 5 for
Type A-1 residential buildings; or

3. Meeting one of the Climate Zone "Single Step Compliance"
Tables; or

4. Georgia Tradeoff Worksheet with Window Takeoff worksheet,
and if applicable the R-value of Wood Stud Walls Worksheet and/or R-value of
Steel Stud Wall Worksheet; or

5. Documentation from an approved software program.*

* Note: MECcheck is an approved software program.
MECcheck may be downloaded free of charge from www.energycodes.gov . (Effective
January 1, 2003)

* Revise Section 602.1 Thermal performance criteria to read
as follows:

602.1 Thermal performance criteria. The minimum
required insulation R-value or maximum required U-factor for each element in
the building thermal envelope (fenestration, roof/ceiling, opaque wall, floor,
slab edge, crawl space wall and basement wall) shall be in accordance with the
criteria in Table 602.1.

Type A-1 residential buildings, with greater than 18-percent
glazing area, Type A-2 residential buildings, with greater than 25-percent
glazing area shall determine compliance using the building envelope
requirements of Chapter 4 or Chapter 5. Remaining sub-sections unchanged.

(Effective January 1, 2003)

* Revise Table 602.1 to read as follows:

(Effective January 1, 2003)

* Delete Section 602.2 Maximum solar heat gain coefficient
for fenestration and substitute the following:

602.2 Maximum solar heat gain coefficient for
fenestration. In all Georgia climate zones (4B through 8), the
area-weighted-average solar heat gain coefficient (SHGC) for glazed
fenestration installed in the building envelope shall not exceed 0.40. This
requirement shall have a delayed implementation date of January 1, 2004.
(Effective January 1, 2003)

CHAPTER 7

BUILDING DESIGN FOR ALL COMMERCIAL
BUILDINGS

SECTION 701

SCOPE

* Revise Section 701.1 General as follows:

701.1 General. Commercial Buildings shall meet
the requirements of ANSI/ASHRAE/IESNA 90.1-2001.
Remaining text unchanged.

(Effective January 1, 2003)

* Add new Section 701.2 Minimum commercial building thermal
component requirements and Table 701 to read as follows:

701.2 Minimum commercial building thermal component
requirements. Table 701 lists the minimum thermal envelope requirements
that shall be met on all commercial buildings for roofs, walls, and glazed
fenestration.

(Effective January 1, 2003)

CHAPTER 8

DESIGN BY ACCEPTABLE PRACTICE FOR COMMERCIAL
BUILDINGS

SECTION 801

SCOPE

* Revise Section 801.2 as follows:

801.2 Application. The requirements in Sections
802, 803, 804, and 805 shall each be satisfied on an individual basis. Where
one or more section(s) is not satisfied, compliance for that section(s) shall
be demonstrated in accordance with the applicable provisions of
ANSI/ASHRAE/IESNA 90.1-2001.

Existing exception unchanged.

(Effective January 1, 2003)

CHAPTER 802

BUILDING ENVELOPE REQUIREMENTS

* Revise Section 802.1 as follows:

802.1 General. Walls, roof assemblies, floors,
glazing, and slabs on grade which are part of the building envelope for
buildings where the window and glazed door area is not greater than 50 percent
of the gross area of above-grade walls shall meet the requirements of Sections
802.2.1 through 802.2.8, as applicable. Buildings with more glazing shall meet
the applicable provisions of ANSI/ASHRAE/ IESNA 90.1-2001.

Remaining text unchanged.

(Effective January 1, 2003)

* Revise Section 802.2 as follows:

802.2 Criteria. The building envelope components
shall meet each of the applicable requirements in Tables 802.2(1), 802.2(2),
802.2(3) and 802.2(4), based on the percentage of wall that is glazed. The
percentage of wall that is glazed shall be determined by dividing the aggregate
area of rough openings for glazing (windows and glazed doors) in all the above
grade walls associated with the building envelope by the total gross area of
all above grade exterior walls that are a part for the building envelope. In
buildings with multiple types of building envelope construction, each building
envelope construction type shall be evaluated separately. Where Tables
802.2(1), 802.2(2), 802.2(3) and 802.2(4) do not list a particular construction
type, the applicable provisions of ANSI/ASHRAE/IESNA 90.1- 2001.
shall be used in lieu of Section 802. Remaining text unchanged.

(Effective January 1, 2003)

* Add new Section 802.3.3 to read as follows:

803.3.3 Dampers integral to the building envelope.
Stair, elevator shaft vents, and other dampers integral to the building
envelope shall be equipped with motorized dampers with a maximum leakage rate
of 3 cfm/ft2 at 1.0 in w.g. (250 Pa) when tested in
accordance with AMCA 500. Such dampers shall be closed during normal building
operation and shall open as required by fire and smoke detection
systems.

Exception: Gravity (non-motorized) dampers are
permitted to be used in buildings less than three stories in height above
grade.

(Effective January 1, 2003)

* Add new Section 802.3.4 to read as follows:

802.3.4 Loading dock weatherseals. Cargo doors
and loading dock doors shall be equipped with weatherseals to resist
infiltration when vehicles are parked in the doorway. (Effective January 1,
2003)

* Add new Section 802.3.5 to read as follows:

802.3.5 Vestibules. A door that separates
conditioned space from the exterior shall be protected with an enclosed
vestibule, with all doors opening into and out of the vestibule equipped with
self-closing devices. Vestibules shall be designed so that in passing through
the vestibule it is not necessary for the interior and exterior doors to open
at the same time.

Exceptions:

1. Buildings in Climate Zone 1A through 4B as indicated in
Table 302.1.

2. Doors not intended to be used as a building entrance door,
such as mechanical or electrical equipment rooms.

3. Doors opening directly from a dwelling unit.

4. Doors that open directly from a space less than 3,000
ft2 (298 m2) in
area.

5. Revolving doors.

6. Doors used primarily to facilitate vehicular movement or
material handling and adjacent personnel doors.

(Effective January 1, 2003)

* Add new Section 802.3.6 to read as follows:

802.3.6 Recessed Lighting Fixtures. When
installed in the building envelope, recessed lighting fixtures shall meet one
of the following requirements:

1. Type IC rated, manufactured with no penetrations between
the inside of the recessed fixture and ceiling cavity and sealed or gasketed to
prevent air leakage into the unconditioned space.

2. Type IC rated, in accordance with ASTM E 283 no more than
2.0 cubic feet per minute (cfm) (0.994 L/s) air movement from the conditioned
space to the ceiling cavity. The lighting fixture shall be tested at 1.57 psi
(75 Pa) pressure difference and shall be labeled. (Effective January 1, 2003)

SECTION 803

BUILDING MECHANICAL SYSTEMS

* Revise Section 803.2.6 as follows:

803.2.6 Cooling with Outdoor air. Each system
over 65,000 Btu/h (19 KW) cooling capacity located in other than Climate Zones
1, 2, 3b, 5a, or 6b as shown in Table 302.1 shall have an economizer that will
automatically shut off the cooling system and allow all of the supply air to be
provided directly from outdoors.

Economizers shall be capable of operating at 100% outside
air, even if additional mechanical cooling is required to meet the cooling load
of the building. Where a single room or space is supplied by multiple air
systems, the aggregate capacity of those systems shall be used in applying this
requirement.

Exceptions:

1. Where the cooling equipment is covered by the minimum
efficiency requirements of Table 803.2.2(1) or 803.2.2(2) and meets the
efficiency requirements of Table 803.2.6.

2. Systems with air or evaporatively cooled condensers and
which serve spaces with open case refrigeration or that require filtration
equipment in order to meet the minimum ventilation requirements of Chapter 4 of
the ICC International Mechanical Code.

3. Systems under 135,000 Btu/h (40 KW) cooling capacity in
Climate Zones 3c, 5b, 7, 13b, and 14. (Effective January 1, 2003)

* Revise Section 803.3.2 as follows:

803.3.2 HVAC equipment performance requirements.
Equipment shall meet the minimum efficiency requirements of Tables
803.2.2(1) through 803.2.2(6) and Table 803.2.2(5), when tested and rated in
accordance with the applicable test procedure. The efficiency shall be verified
through certification under an approved certification program, or if no
certification program exists, the equipment efficiency ratings shall be
supported by data furnished by the manufacturer. Where multiple rating
conditions and/or performance requirements are provided, the equipment shall
satisfy all stated requirements. Where components, such as indoor or outdoor
coils, from different manufacturers are used, calculations and supporting data
shall be furnished by the designer that demonstrate the combined efficiency of
the specified components meets the requirements herein.

Where unitary or prepackaged equipment is used in a complex
HVAC system and is not covered by Section 803.3.2, the equipment shall meet the
applicable requirements of Section 803.2.2.

Exception:

Equipment listed in Table 803.2.2(2) not designed for
operation at ARI standard test conditions of 44° F (7° C) leaving chilled water
temperature and 85° (29° C) entering condenser water temperature shall have a
minimum full load COP and IPLV rating as shown in Tables 803.3.2(3) through
803.3.2(5) as applicable. The table values are only applicable over the
following full load design ranges:

1. Leaving Chilled Water Temperature: 40 to 48° F (4 C to 9°
C).

2. Entering Condenser Water Temperature: 75 to 85° F (24 C to
29° C). Chillers designed to operate outside of these ranges are not covered by
this code. Condensing Water Temperature Rise: 5 to 15° F (-15 to -9° C).
(Effective January 1, 2003)

* Delete Tables 803.2.2(1) through 803.2.2(5) and substitute
to read as follows and add the following new Tables 803.3.2(1) through
803.3.2(3):

(Effective January 1, 2003)

* Revise Section 803.3.3.5 as follows:

803.3.3.5 Economizers. Economizers shall be
provided on each system over 65,000 Btu/h (19 kW) cooling capacity in
accordance with Section 803.2.6.

Exceptions:

Water economizers that are capable of cooling supply air by
direct and/or indirect evaporation and providing up to 100% of the expected
system cooling load at outside air temperatures of 50° F (10° C) dry bulb/45° F
(7.2° C) wet bulb and below.

Systems under 135,000 Btu/h (40 kW) cooling capacity in
Climate Zones 3c, 5b, 7, 13b, and 14.

(Effective January 1, 2003)

* Add new Section 803.3.3.8 to read as follows:

803.3.3.8 Heat rejection equipment fan speed control.
Each fan powered by a motor of 7.5 hp (5.6 kW) or larger shall have the
capability to operate that fan at two-thirds of full speed or less, and shall
have controls that automatically change the fan speed to control the leaving
fluid temperature or condensing temperature/pressure of the heat rejection
device.

Exception: Factory-installed heat rejection
devices within HVAC equipment tested and rated in accordance with Tables
803.3.2(1) through 803.3.2(3).

(Effective January 1, 2003)

* Delete Section 803.3.4.1 Temperature reset for air systems
without substitution. (Effective January 1, 2003)

SECTION 805

LIGHTING SYSTEMS

* Revise Section 805.2 as follows:

805.2 Lighting controls. Lighting systems shall
be provided with controls as required in Sections 805.2.1, 805.2.2, and
805.2.3.

(Effective January 1, 2003)

* Add new Section 805.2.3 to read as follows:

805.2.3 Additional controls. Each area that is
required to have a manual control shall have additional controls that meet the
requirements of Sections 805.2.3.1, 805.2.3.2, or 805.2.3.3.

Exceptions:

1. Areas that have only 1 luminaire.

2. Areas that are controlled by an occupant-sensing
device.

3. Corridors, storerooms, restrooms, or public lobbies.
(Effective January 1, 2003)

* Add new Sections 805.2.3.1, 805.2.3.2 and 805.2.3.3 as
follows:

805.2.3.1 Bi-level Switching. Each area less
than 250 ft2 (23 m2) that
is required to have a manual control shall also allow the occupant to reduce
the connected lighting load in a reasonably uniform illumination pattern by at
least 50 percent.

Exceptions:

1. Areas that have only one luminaire.

2. Areas that are controlled by an occupant-sensing
device.

3. Corridors, storerooms, restrooms, or public
lobbies.

4. Guest rooms.

805.2.3.2 Automatic lighting shutoff. Buildings
larger than 5,000 ft2 shall be equipped with an automatic control device to
shut off lighting in all spaces. This automatic control device shall function
on either:

1. A scheduled basis, using time-of-day, with an independent
program schedule that controls the interior lighting in areas that do not
exceed 25,000 ft2 and are not more than one floor,
or

2. An unscheduled basis by occupant intervention.

805.2.3.3 Guest rooms. Guest rooms in hotels,
motels, boarding houses, or similar buildings shall have at least one master
switch at the main entry door that controls all permanently wired lighting
fixtures and switched receptacles, except those in the bathroom(s). Suites
shall have a control meeting these requirements at the entry to each room or at
the primary entry to the suite.

(Effective January 1, 2003)

CHAPTER 9

REFERENCED STANDARDS

Revise Chapter 9 to add the following:

ANSI/ASHRAE/IESNA
90.1-2001

Energy Standard for Buildings

except Low-Rise Residential

Buildings

ASHRAE-2001

Handbook Fundamentals

NEMA TP1-1996

Guide for Determining Energy

Efficiency for Distribution

Transformers

NEMA TP2-1998

Standard Test Method for

Measuring the Energy

Consumption of Distribution

Transformers

NEMA TP3-2000

Standard for the Labeling of

Distribution Transformer

Efficiency

Remaining text unchanged.

(Effective January 1, 2003)

* Add Figure 9-1 F2-values for Slab-on-Grade Perimeter
Insulation and Figure 9-2 Component Performance Table to read as
follows:

(Effective January 1, 2003)

APPENDIX

* Revise Appendix to read as follows:

Change all references for existing Appendix to "Appendix
A".

* Add new Appendix B to read as follows:

APPENDIX B

Throughout this Appendix there is information that may be
helpful in meeting and understanding the Georgia State Energy Code. In cases of
conflict, refer to the 2000 International Energy Conservation Code for
clarification.

CHECKLIST

Wood Framing

Low Rise Residential Use

To be filled out by permit applicant and presented to
Building Department at time permit is requested. A copy will be available at
the job site for CEO (Code Enforcement Officers) review.

WINDOW PRODUCT RATING, CERTIFICATION, AND
LABELING

The Georgia Energy Code, Section 102.5.2 requires that
fenestration products, (window, glass door and skylight) shall be labeled with
its U-factor and Solar Heat Gain Coefficient (SHGC). Fenestration products'
U-factor and SHGC shall be determined by an accredited, independent laboratory
in accordance with NFRC 100 for Ufactor and NFRC 200 for SHGC, or from default
values from Table 102.5.2(1) for U-factor and Table 102.5.2(3) for SHGC.
Manufacturers that label their products with NFRC U-factors and SHGCs shall
either use an NFRC label (see sample NFRC label below) or a label of their own
design. The label shall list as a minimum: U-factor, SHGC, frame type, number
of panes of glazing, whether the window is fixed or operable, and the type of
glazing tint, if present. The label shall contain the words "Meets Thermal
Break Criteria" if the product claims a U-factor based on a thermal-break
product.

National Fenestration Rating Council (NFRC) - U-factor
and SHGC

Below is a sample window label of NFRC-determined energy
performance values that code officials should look for during
inspections:

Note: This sample window label also contains "Visible
Transmittance" (VT) performance values. The Georgia Energy Code does not
establish minimum requirements for VT, but this and other information that
might be useful to builders, designers, consumers, and others (like air leakage
rates) may also be present on labels used by some manufacturers.

Default U-factor and SHGC

If NFRC 100 or NFRC 200 are not used to determine product
Ufactor and SHGC, then manufacturers shall obtain default values from Table
102.5.2(1) for U-factor and Table 102.5.2(3) for SHGC and label the product
with a "Default Window Label." Manufacturers or assemblers shall label their
products with default U-factors and SHGCs, for example, site built and shop
assembled windows without NFRC labels, shall follow the format of the sample
default label below. This label shall list as a minimum: Default U-factor from
Table 102.5.2(1), Default SHGC from Table 102.5.2(3), frame type, number of
panes of glazing, whether the window is fixed or operable, and the type of
glazing tint, if present. The label shall contain the words,"Meets Thermal
Break Criteria" if the product claims a U-factor based on a thermal-break
product:

<<Sample Window Label of DEFAULT

Energy Performance Values>>

Table 502.2.3.1(1b)

Wall R-value 35/8'' Steel Stud 16'' OC (Insulation plus
sheathing)

"Single-Step" Residential Energy Code Compliance
Climate Zone 4B - South Georgia - Option 4B-1

You are "deemed to comply" with the Georgia State
Energy Code for Buildings if your residential structure meets the
following conditions:

1. Your building shall be a one or two family detached
dwelling built using wood framing.

2. Your building is three stories or less in height and not
larger than 5,000 square feet of conditioned area.

3. Your building site must be located in Climate Zone 4B, as
shown in the IECC 2000 Figure 302.1(11), an area of the state where the
climatic conditions of approximately 2,000 Heating Degree Days or less
apply.

4. You shall not make any substitutions of any kind for
R-values/ U-factors listed below.

5. Your window and door openings shall not exceed 18 percent
of the gross wall area.

6. You shall comply with code requirements for envelope air
sealing including all air tight, I.C. rated light fixtures in ceilings with
attics and seal all ductwork with mastic.

7. Equipment minimum efficiencies shall be observed: Gas
furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0;

Heat pump: HSPF 6.8; other (explain) _________________

% Openings in gross area of exterior
wall1 18% Max.

Doors U-factor 0.55 Max.

Windows, Double Pane, U-factor2
0.65 Max.

Solar Heat Gain Coefficient
(SHGC)2 0.40 Max.

Ceiling insulation3 R-30

Wall cavity insulation R-13

Knee Wall insulation R-19

Wall Sheathing4 Plywood/OSB

Floor insulation R-11

Basement Masonry wall insulation R-5

Slab Perimeter insulation5 R-0

___________________

1. "% Openings" is defined by the total area of the openings
of windows and doors divided by the total gross area of the exterior wall. %
Openings = 100 × (windows + doors) / (opaque walls + windows + doors).

2. Up to 5% of the window area may be exempt from meeting the
window U-factor and SHGC requirements to allow for decorative glazing.

3. Sloped ceilings, such as cathedral & tray ceilings,
which require batt insulation, may be insulated with R-19 batts, provided the
R-19 portion does not exceed 25% of the total ceiling area and provided that
the flat portions of the ceiling are insulated to R-30.

4. Insulating values for plywood, OSB or other structural
sheathing are already accounted for in the approach. Garage walls may be R-13
cavity insulation with gypsum on both sides.

5. Unheated slabs.

All R-values shall be printed on the actual insulation and be
stabilized R-values all Windows shall have labels listing U-factor, SHGC, and
Key Features

Foam Plastics shall not be installed below grade
on foundation walls or below grade on slab foundations. These R-values may
result in some degree of "over-design". However, this method will apply to a
majority of one and two family residences built in South Georgia. If you must
change one or more of the R-values/U-factors listed to a lower R-value or
higher U-factor, then do not use this method. No substitutions are
allowed here.

Instead, you may use one of the other methods to show
compliance, such as the Tradeoff Worksheet or the free MECcheck software
(available at www.energycodes.gov).
You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with
Georgia modifications.

At the time a permit is requested, you shall show how you
plan to meet the Georgia Energy Code. When using the
"Single-Step" Residential Energy Code Compliance
method, you may not be required to turn in additional paperwork to
obtain a building permit.

"Single-Step" Residential Energy Code Compliance
Climate Zone 5A - South Central Georgia - Option 5A-1

You are "deemed to comply" with the Georgia State
Energy Code for Buildings if your residential structure meets the
following conditions:

1. Your building shall be a one or two family detached
dwelling built using wood framing.

2. Your building is three stories or less in height and not
larger than 5,000 square feet of conditioned area.

3. Your building site must be located in Climate Zone 5A, as
shown in the IECC 2000 Figure 302.1(11), an area of the state where the
climatic conditions of approximately 2,500 Heating Degree Days or less
apply.

4. You shall not make any substitutions of any kind for
R-values/ U-factors listed below.

5. Your window and door openings shall not exceed 18 percent
of the gross wall area.

6. You shall comply with code requirements for envelope air
sealing including all air tight, I.C. rated light fixtures in ceilings with
attics and seal all ductwork with mastic.

7. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER
10.0;

Heat pump: HSPF 6.8; other (explain) ______________

% Openings in gross area of exterior
wall1 18% Max.

Doors U-factor 0.55 Max.

Windows, Double Pane, U-factor2
0.60 Max.

Solar Heat Gain Coefficient
(SHGC)2 0.40 Max.

Ceiling insulation3 R-30

Wall cavity insulation R-13

Knee Wall insulation R-19

Wall Sheathing4 Plywood/OSB

Floor Insulation R-11

Basement Masonry wall insulation R-5

Slab Perimeter insulation5 R-0

___________________

1. "% Openings" is defined by the total area of the openings
of windows and doors divided by the total gross area of the exterior wall. %
Openings = 100 × (windows + doors) / (opaque walls + windows + doors).

2. Up to 5% of the window area may be exempt from meeting the
window U-factor and SHGC requirements to allow for decorative glazing.

3. Sloped ceilings, such as cathedral & tray ceilings,
which require batt insulation, may be insulated with R-19 batts, provided the
R-19 portion does not exceed 25% of the total ceiling area and provided the
flat portions of the ceiling are insulated to R-30.

4. Insulating values for plywood, OSB or other structural
sheathing are already accounted for in the approach. Garage walls may be R-13
cavity insulation with gypsum on both sides.

5. Unheated slabs.

All R-values shall be printed on the actual insulation and be
stabilized R-values All Windows shall have labels listing U-factor, SHGC, and
Key Features

Foam Plastics shall not be installed below grade
on foundation walls or below grade on slab foundations. These R-values may
result in some degree of "over-design". However, this method will apply to a
majority of one and two family residences built in South Central Georgia. If
you must change one or more of the R-values/U-factors listed to a lower R-value
or higher U-factor, then do not use this method. No substitutions are
allowed here.

Instead, you may use one of the other methods to show
compliance, such as the Tradeoff Worksheet or the free MECcheck software
(available at www.energycodes.gov).
You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with
Georgia modifications.

At the time a permit is requested, you shall show how you
plan to meet the Georgia Energy Code. When using the
"Single-Step" Residential Energy Code Compliance
method, you may not be required to turn in additional paperwork to
obtain a building permit.

"Single-Step" Residential Energy Code Compliance
Climate Zone 6B - Central Georgia - Option 6B-1 (R-30 ceiling, R-13 batt + R-2
sheathing, 0.55=Uwindow)

You are "deemed to comply" with the Georgia State
Energy Code for Buildings if your residential structure meets the
following conditions:

1. Your building shall be a one or two family detached
dwelling built using wood framing.

2. Your building is three stories or less in height and not
larger than 5,000 square feet of conditioned area.

3. Your building site must be located in Climate Zone 6B, as
shown in the IECC 2000 Figure 302.1(11), an area of the state where the
climatic conditions of approximately 3,000 Heating Degree Days or less
apply.

4. You shall not make any substitutions of any kind for
R-values/ U-factors listed below.

5. Your window and door openings shall not exceed 18 percent
of the gross wall area.

6. You shall comply with code requirements for envelope air
sealing including all air tight, I.C. rated light fixtures in ceilings with
attics and seal all ductwork with mastic.

7. Equipment minimum efficiencies shall be observed: Gas
furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other
(explain) __________

% Openings in gross area of exterior
wall1 18% Max.

Doors U-factor 0.55 Max.

Windows, Double Pane, U-factor2
0.55 Max.

Solar Heat Gain Coefficient
(SHGC)2 0.40 Max.

Ceiling insulation3 R-30

Wall cavity insulation R-13

Knee Wall insulation R-19

Insulating Sheathing4 R-2

Floor Insulation R-19

Basement Masonry wall insulation R-6

Slab Perimeter insulation5
R-0

___________________

1. "% Openings" is defined by the total area of the openings
of windows and doors divided by the total gross area of the exterior wall. %
Openings = 100 × (windows + doors) / (opaque walls + windows + doors).

2. Up to 5% of the window area may be exempt from meeting the
window U-factor and SHGC requirements to allow for decorative glazing.

3. Sloped ceilings, such as cathedral & tray ceilings,
which require batt insulation, may be insulated with R-19 batts, provided the
R-19 portion does not exceed 25% of the total ceiling area and provided the
flat portions of the ceiling are insulated to R-30.

4. When the Exterior Wall R-value is cavity insulation and
continuous insulated sheathing, 25% of the gross wall area may be Plywood/OSB
(for corner bracing/structural requirements) or gypsum fastened direct to the
garage wall studs.

5. Unheated slabs.

All R-values shall be printed on the actual insulation and be
stabilized R-values all Windows shall have labels listing U-factor, SHGC, and
Key Features

Foam Plastics shall not be installed below grade
on foundation walls or below grade on slab foundations. These R-values may
result in some degree of "over-design". However, this method will apply to a
majority of one and two family residences built in Central Georgia. If you must
change one or more of the R-values/U-factors listed to a lower R-value or
higher U-factor, then do not use this method. No substitutions are
allowed here.

Instead, you may use one of the other methods to show
compliance, such as the Tradeoff Worksheet or the free MECcheck software
(available at www.energycodes.gov).
You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with
Georgia modifications.

At the time a permit is requested, you shall show how you
plan to meet the Georgia Energy Code. When using the
"Single-Step" Residential Energy Code Compliance
method, you may not be required to turn in additional paperwork to
obtain a building permit.

"Single-Step" Residential Energy Code Compliance
Climate Zone 6B - Central Georgia - Option 6B-2 (R-38 ceiling, R-13 batt,
0.55=Uwindow)

You are "deemed to comply" with the Georgia State
Energy Code for Buildings if your residential structure meets the
following conditions:

1. Your building shall be a one or two family detached
dwelling built using wood framing.

2. Your building is three stories or less in height and not
larger than 5,000 square feet of conditioned area.

3. Your building site must be located in Climate Zone 6B, as
shown in the IECC 2000 Figure 302.1(11), an area of the state where the
climatic conditions of approximately 3,000 Heating Degree Days or less
apply.

4. You shall not make any substitutions of any kind for
R-values/ U-factors listed below.

5. Your window and door openings shall not exceed 18 percent
of the gross wall area.

6. You shall comply with code requirements for envelope air
sealing including all air tight, I.C. rated light fixtures in ceilings with
attics and seal all ductwork with mastic.

7. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat
pump: HSPF 6.8; other (explain) % _____________________

Openings in gross area of exterior
wall1 18% Max.

Doors U-factor 0.55 Max.

Windows, Double Pane, U-factor2
0.55 Max.

Solar Heat Gain Coefficient
(SHGC)2 0.40 Max.

Ceiling insulation3 R-38

Wall cavity insulation R-13

Knee Wall insulation R-19

Wall Sheathing 4
Plywood/OSB

Insulating Sheathing4 R-3

Floor Insulation R-19

Basement Masonry wall insulation R-6

Slab Perimeter insulation5
R-0

___________________

1. "% Openings" is defined by the total area of the openings
of windows and doors divided by the total gross area of the exterior wall. %
Openings = 100 × (windows + doors) / (opaque walls + windows + doors).

2. Up to 5% of the window area may be exempt from meeting the
window U-factor and SHGC requirements to allow for decorative glazing.

3. Sloped ceilings, such as cathedral & tray ceilings,
which require batt insulation, may be insulated with R-19 batts, provided the
R-19 portion does not exceed 25% of the total ceiling area and provided the
flat portions of the ceiling are insulated to R-30.

4. Insulating values for plywood, OSB or other structural
sheathing are already accounted for in the approach. Garage walls may be R-13
cavity insulation with gypsum on both sides.

5. Unheated slabs.

All R-values shall be printed on the actual insulation and be
stabilized R-values all Windows shall have labels listing U-factor, SHGC, and
Key Features

Foam Plastics shall not be installed below grade
on foundation walls or below grade on slab foundations. These R-values may
result in some degree of "over-design". However, this method will apply to a
majority of one and two family residences built in Central Georgia. If you must
change one or more of the R-values/U-factors listed to a lower R-value or
higher U-factor, then do not use this method. No substitutions are
allowed here.

Instead, you may use one of the other methods to show
compliance, such as the Tradeoff Worksheet or the free MECcheck software
(available at www.energycodes.gov).
You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with
Georgia modifications.

At the time a permit is requested, you shall show how you
plan to meet the Georgia Energy Code. When using the
"Single-Step" Residential Energy Code Compliance
method, you may not be required to turn in additional paperwork to
obtain a building permit.

"Single-Step" Residential Energy Code Compliance
Climate Zone 7A - Greater Atlanta Area - Option 7A-1 (R-30 ceiling, R-13 batt +
R-3 sheathing, 0.55=Uwindow)

You are "deemed to comply" with the Georgia State
Energy Code for Buildings if your residential structure meets the
following conditions:

1. Your building shall be a one or two family detached
dwelling built using wood framing.

2. Your building is three stories or less in height and not
larger than 5,000 square feet of conditioned area.

3. Your building site must be located in Climate Zone 7A, as
shown in the IECC 2000 Figure 302.1(11), an area of the state where the
climatic conditions of approximately 3,500 Heating Degree Days or less
apply.

4. You shall not make any substitutions of any kind for
R-values/ U-factors listed below.

5. Your window and door openings shall not exceed 18 percent
of the gross wall area.

6. You shall comply with code requirements for envelope air
sealing including all air tight, I.C. rated light fixtures in ceilings with
attics and seal all ductwork with mastic.

7. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat
pump: HSPF 6.8; other (explain) __________________________

% Openings in gross area of exterior
wall1 18% Max.

Doors U-factor 0.35 Max.

Windows, Double Pane, U-factor2
0.55 Max.

Solar Heat Gain Coefficient
(SHGC)2 0.40 Max.

Ceiling insulation3 R-30

Wall cavity insulation R-13

Knee Wall insulation R-19

Insulating Sheathing4 R-3

Floor Insulation R-19

Basement Masonry wall insulation R-7

Slab Perimeter insulation5
R-0

___________________

1. "% Openings" is defined by the total area of the openings
of windows and doors divided by the total gross area of the exterior wall. %
Openings = 100 × (windows + doors) / (opaque walls + windows + doors).

2. Up to 5% of the window area may be exempt from meeting the
window U-factor and SHGC requirements to allow for decorative glazing.

3. Sloped ceilings, such as cathedral & tray ceilings,
which require batt insulation, may be insulated with R-19 batts, provided the
R-19 portion does not exceed 25% of the total ceiling area and provided the
flat portions of the ceiling are insulated to obtain full height R-30.

4. When the Exterior Wall R-value is cavity insulation and
continuous insulated sheathing, 25% of the gross wall area may be Plywood/OSB
(for corner bracing/structural requirements) or gypsum fastened direct to the
garage wall studs.

5. Unheated slabs.

All R-values shall be printed on the actual insulation and be
stabilized R-values all Windows shall have labels listing U-factor, SHGC, and
Key Features

Foam Plastics shall not be installed below grade
on foundation walls or below grade on slab foundations. These R-values may
result in some degree of "over-design". However, this method will apply to a
majority of one and two family residences built in the Greater Atlanta area. If
you must change one or more of the R-values/U-factors listed to a lower R-value
or higher U-factor, then do not use this method. No substitutions are
allowed here.

Instead, you may use one of the other methods to show
compliance, such as the Tradeoff Worksheet or the free MECcheck software
(available at www.energycodes.gov).
You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with
Georgia modifications.

At the time a permit is requested, you shall show how you
plan to meet the Georgia Energy Code. When using the
"Single-Step" Residential Energy Code Compliance
method, you may not be required to turn in additional paperwork to
obtain a building permit.

"Single-Step" Residential Energy Code
Compliance

Climate Zone 7A - Greater Atlanta Area - Option
7A-2

(R-38 ceiling, R-15 batt + OSB/Plywood)

You are "deemed to comply" with the Georgia State
Energy Code for Buildings if your residential structure meets the
following conditions:

1. Your building shall be a one or two family detached
dwelling built using wood framing.

2. Your building is three stories or less in height and not
larger than 5,000 square feet of conditioned area.

3. Your building site must be located in Climate Zone 7A, as
shown in the IECC 2000 Figure 302.1(11), an area of the state where the
climatic conditions of approximately 3,500 Heating Degree Days or less
apply.

4. You shall not make any substitutions of any kind for
R-values/ U-factors listed below.

5. Your window and door openings shall not exceed 18 percent
of the gross wall area.

6. You shall comply with code requirements for envelope air
sealing including all air tight, I.C. rated light fixtures in ceilings with
attics and seal all ductwork with mastic.

7. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat
pump: HSPF 6.8; other (explain) ___________________________

% Openings in gross area of exterior
wall1 18% Max.

Doors U-factor 0.35 Max.

Windows, Double Pane, U-factor2
0.55 Max.

Solar Heat Gain Coefficient
(SHGC)2 0.40 Max.

Ceiling insulation3 R-38

Wall cavity insulation R-15

Knee Wall insulation R-19

Wall Sheathing4 Plywood/OSB

Floor Insulation R-19

Basement Masonry wall insulation R-7

Slab Perimeter insulation5
R-0

___________________

1. "% Openings" is defined by the total area of the openings
of windows and doors divided by the total gross area of the exterior wall. %
Openings = 100 × (windows + doors) / (opaque walls + windows + doors).

2. Up to 5% of the window area may be exempt from meeting the
window U-factor and SHGC requirements to allow for decorative glazing.

3. Sloped ceilings, such as cathedral & tray ceilings,
which require batt insulation, may be insulated with R-19 batts, provided the
R-19 portion does not exceed 25% of the total ceiling area and provided the
flat portions of the ceiling are insulated to R-38.

4. Insulating values for plywood, OSB or other structural
sheathing are already accounted for in the approach. Garage walls may be R-13
cavity insulation with gypsum on both sides.

5. Unheated slabs.

All R-values shall be printed on the actual insulation and be
stabilized R-values all Windows shall have labels listing U-factor, SHGC, and
Key Features

Foam Plastics shall not be installed below grade
on foundation walls or below grade on slab foundations. These R-values may
result in some degree of "over-design". However, this method will apply to a
majority of one and two family residences built in the Greater Atlanta area. If
you must change one or more of the R-values/U-factors listed to a lower R-value
or higher U-factor, then do not use this method. No substitutions are
allowed here.

Instead, you may use one of the other methods to show
compliance, such as the Tradeoff Worksheet or the free MECcheck software
(available at www.energycodes.gov).
You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with
Georgia modifications.

At the time a permit is requested, you shall show how you
plan to meet the Georgia Energy Code. When using the
"Single-Step" Residential Energy Code Compliance
method, you may not be required to turn in additional paperwork to
obtain a building permit.

"Single-Step" Residential Energy Code
Compliance

Climate Zone 7A - Greater Atlanta Area - Option
7A-3

(R-30 ceiling, R-13 batt, 0.45=Uwindow)

You are "deemed to comply" with the Georgia State
Energy Code for Buildings if your residential structure meets the
following conditions:

1. Your building shall be a one or two family detached
dwelling built using wood framing.

2. Your building is three stories or less in height and not
larger than 5,000 square feet of conditioned area.

3. Your building site must be located in Climate Zone 7A, as
shown in the IECC 2000 Figure 302.1(11), an area of the state where the
climatic conditions of approximately 3,500 Heating Degree Days or less
apply.

4. You shall not make any substitutions of any kind for
R-values/ U-factors listed below.

5. Your window and door openings shall not exceed 18 percent
of the gross wall area.

6. You shall comply with code requirements for envelope air
sealing including all air tight, I.C. rated light fixtures in ceilings with
attics and seal all ductwork with mastic.

7. Equipment minimum efficiencies shall be observed:

8. Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0;
Heat pump: HSPF 6.8; other (explain) _____________________________

% Openings in gross area of exterior
wall1 18% Max.

Doors U-factor 0.55 Max.

Windows, Double Pane, U-factor2
0.45 Max.

Solar Heat Gain Coefficient
(SHGC)2 0.40 Max.

Ceiling insulation3 R-30

Wall cavity insulation R-13

Knee Wall insulation R-19

Wall Sheathing4 Plywood/OSB

Floor Insulation R-19

Basement Masonry wall insulation R-7

Slab Perimeter insulation5
R-0

___________________

1. "% Openings" is defined by the total area of the openings
of windows and doors divided by the total gross area of the exterior wall. %
Openings = 100 × (windows + doors) / (opaque walls + windows + doors).

2. Up to 5% of the window area may be exempt from meeting the
window U-factor and SHGC requirements to allow for decorative glazing.

3. Sloped ceilings, such as cathedral & tray ceilings,
which require batt insulation, may be insulated with R-19 batts, provided the
R-19 portion does not exceed 25% of the total ceiling area and provided the
flat portions of the ceiling are insulated to R-30. 4. Insulating values for
plywood, OSB or other structural sheathing are already accounted for in the
approach. Garage walls may be R-13 cavity insulation with gypsum on both sides.

5. Unheated slabs.

All R-values shall be printed on the actual insulation and be
stabilized R-values all Windows shall have labels listing U-factor, SHGC, and
Key Features

Foam Plastics shall not be installed below grade
on foundation walls or below grade on slab foundations. These R-values may
result in some degree of "over-design". However, this method will apply to a
majority of one and two family residences built in the Greater Atlanta area. If
you must change one or more of the R-values/U-factors listed to a lower R-value
or higher U-factor, then do not use this method. No substitutions are
allowed here.

Instead, you may use one of the other methods to show
compliance, such as the Tradeoff Worksheet or the free MECcheck software
(available at www.energycodes.gov).
You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with
Georgia modifications.

At the time a permit is requested, you shall show how you
plan to meet the Georgia Energy Code. When using the
"Single-Step" Residential Energy Code Compliance
method, you may not be required to turn in additional paperwork to
obtain a building permit.

"Single-Step" Residential Energy Code ComplianceClimate Zone 8 - North Georgia - Option 8-1

(R-38 ceiling, R-13 batt + R-3 Sheathing)

You are "deemed to comply" with the Georgia State
Energy Code for Buildings if your residential structure meets the
following conditions:

1. Your building shall be a one or two family detached
dwelling built using wood framing.

2. Your building is three stories or less in height and not
larger than 5,000 square feet of conditioned area.

3. Your building site must be located in Climate Zone 8, as
shown in the IECC 2000 Figure 302.1(11), an area of the state where the
climatic conditions of approximately 4,000 Heating Degree Days or less
apply.

4. You shall not make any substitutions of any kind for
R-values/ U-factors listed below.

5. Your window and door openings shall not exceed 18 percent
of the gross wall area.

6. You shall comply with code requirements for envelope air
sealing including all air tight, I.C. rated light fixtures in ceilings with
attics and seal all ductwork with mastic.

7. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat
pump: HSPF 6.8; other (explain) _________________________

% Openings in gross area of exterior
wall1 18% Max.

Doors U-factor 0.55 Max.

Windows, Double Pane, U-factor2
0.50 Max.

Solar Heat Gain Coefficient
(SHGC)2 0.40 Max.

Ceiling insulation3 R-38

Wall cavity insulation R-13

Knee Wall insulation R-19

Insulating Sheathing4 R-3

Floor Insulation R-19

Basement Masonry wall insulation R-8

Slab Perimeter insulation5
R-0

___________________

1. "% Openings" is defined by the total area of the openings
of windows and doors divided by the total gross area of the exterior wall. %
Openings = 100 × (windows + doors) / (opaque walls + windows + doors).

2. Up to 5% of the window area may be exempt from meeting the
window U-factor and SHGC requirements to allow for decorative glazing.

3. Sloped ceilings, such as cathedral & tray ceilings,
which require batt insulation, may be insulated with R-19 batts, provided the
R-19 portion does not exceed 25% of the total ceiling area and provided the
flat portions of the ceiling are insulated to R-38. 4. When the exterior Wall
R-value is cavity insulation and continuous insulated sheathing, 25% of the
gross wall area may be Plywood/OSB (for corner bracing/structural requirements)
or gypsum fastened direct to the garage wall studs.

5. Unheated slabs.

All R-values shall be printed on the actual insulation and be
stabilized R-values all Windows shall have labels listing U-factor, SHGC, and
Key Features

Foam Plastics shall not be installed below grade
on foundation walls or below grade on slab foundations. These R-values may
result in some degree of "over-design". However, this method will apply to a
majority of one and two family residences built in North Georgia. If you must
change one or more of the R-values/U-factors listed to a lower R-value or
higher U-factor, then do not use this method. No substitutions are
allowed here.

Instead, you may use one of the other methods to show
compliance, such as the Tradeoff Worksheet or the free MECcheck software
(available at www.energycodes.gov).
You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with
Georgia modifications.

At the time a permit is requested, you shall show how you
plan to meet the Georgia Energy Code. When using the
"Single-Step" Residential Energy Code Compliance
method, you may not be required to turn in additional paperwork to
obtain a building permit.

"Single-Step" Residential Energy Code
Compliance

Climate Zone 8 - North Georgia - Option
8-2

(R-38 ceiling, R-13 batt + OSB/Plywood)

You are "deemed to comply" with the Georgia State
Energy Code for Buildings if your residential structure meets the
following conditions:

1. Your building shall be a one or two family detached
dwelling built using wood framing.

2. Your building is three stories or less in height and not
larger than 5,000 square feet of conditioned area.

3. Your building site must be located in Climate Zone 8, as
shown in the IECC 2000 Figure 302.1(11), an area of the state where the
climatic conditions of approximately 4,000 Heating Degree Days or less
apply.

4. You shall not make any substitutions of any kind for
R-values/ U-factors listed below.

5. Your window and door openings shall not exceed 18 percent
of the gross wall area.

6. You shall comply with code requirements for envelope air
sealing including all air tight, I.C. rated light fixtures in ceilings with
attics and seal all ductwork with mastic.

7. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat
pump: HSPF 6.8; other (explain) _________________________

% Openings in gross area of exterior
wall1 18% Max.

Doors U-factor 0.35 Max.

Windows, Double Pane, U-factor2
0.45 Max.

Solar Heat Gain Coefficient
(SHGC)2 0.40 Max.

Ceiling insulation3 R-38

Wall cavity insulation R-13

Knee Wall insulation R-19

Wall Sheathing4 Plywood/OSB

Floor Insulation R-19

Basement Masonry wall insulation R-8

Slab Perimeter insulation5
R-0

___________________

1. "% Openings" is defined by the total area of the openings
of windows and doors divided by the total gross area of the exterior wall. %
Openings = 100 × (windows + doors) / (opaque walls + windows + doors).

2. Up to 5% of the window area may be exempt from meeting the
window U-factor and SHGC requirements to allow for decorative glazing.

3. Sloped ceilings, such as cathedral & tray ceilings,
which require batt insulation, may be insulated with R-19 batts, provided the
R-19 portion does not exceed 25% of the total ceiling area and provided the
flat portions of the ceiling are insulated to R-38. 4. Insulating values for
plywood, OSB or other structural sheathing are already accounted for in the
approach. Garage walls may be R-13 cavity insulation with gypsum on both sides.

5. Unheated slabs.

All R-values shall be printed on the actual insulation and be
stabilized R-values all Windows shall have labels listing U-factor, SHGC, and
Key Features

Foam Plastics shall not be installed below grade
on foundation walls or below grade on slab foundations. These R-values may
result in some degree of "over-design". However, this method will apply to a
majority of one and two family residences built in North Georgia. If you must
change one or more of the R-values/U-factors listed to a lower R-value or
higher U-factor, then do not use this method. No substitutions are
allowed here.

Instead, you may use one of the other methods to show
compliance, such as the Tradeoff Worksheet or the free MECcheck software
(available at www.energycodes.gov).
You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with
Georgia modifications.

At the time a permit is requested, you shall show how you
plan to meet the Georgia Energy Code. When using the
"Single-Step" Residential Energy Code Compliance
method, you may not be required to turn in additional paperwork to
obtain a building permit.

Appendix

BUILDING ENVELOPE

The elements of a building which enclose conditioned spaces
through which thermal energy is capable of being transferred to or from the
exterior or to or from spaces exempted by the provisions of Section 101.4.1.
-2000 IECC

The building envelope is the barrier that
separates the conditioned space from the outside or unconditioned spaces. The
building envelope consists of two parts - an air barrier and a thermal barrier
that must be both continuous and contiguous (touching each other). In a typical
residence, the building envelope consists of the roof, walls, windows, doors,
and foundation. Examples of unconditioned spaces include attics, vented
crawlspaces, basements with ceiling insulation and no HVAC supply registers,
and garages.

* Note: An attic knee wall is any vertical wall that
separates conditioned space from an unconditioned attic. In Georgia, knee walls
must be insulated to R-19. An attic-side air barrier (OSB, foil-faced
sheathing, etc.) is recommended.

** Note: Although there is nothing to prevent the garage
walls from being insulated, due to indoor air quality concerns, the garage
should never be considered inside the building envelope.

"SINGLE-STEP" COMPLIANCE

FOR SIMPLE COMMERCIAL BUILDINGS

The Single-Step compliance procedure is available only for
small commercial buildings with simple HVAC systems. If you demonstrate that
your building complies with this procedure, you are deemed to comply with the
Georgia State Energy Code. You shall complete the documentation on all
of the enclosed forms for Envelope, Lighting, and HVAC and Water Heating
systems and equipment.

Eligible buildings shall meet all of the
following requirements:

1) Two stories or less.

2) 25,000 ft2 or less gross floor area.

3) Maximum glazing area is 25% of the above-grade gross wall
area.

4) Each HVAC system serves a single zone, controlled by a
single thermostat in the zone being served.

5) Cooling (if any) is provided by one or more air-cooled
(unitary packaged or split system) air conditioners or geothermal heat pumps
that do not exceed 20 tons (each).*

6) Primary heating (if any) is provided by one or more
air-cooled (unitary packaged or split system) heat pumps (with internal
supplemental electrical resistance heat, if needed), geothermal heat pumps, or
fuel-fired furnaces. Supplemental individual electric resistance heaters are
limited to a maximum of 5 kW each.*

7) The outside air quality is 3,000 cfm or less and shall be
less than 70% of the total supply air.

* Note: Hydronic or steam distribution systems are not
permitted under this Single Step approach.

Failure to meet all of the above criteria precludes use of
the Single Step compliance forms. All other commercial buildings shall
demonstrate compliance with any of the other compliance pathways of the Georgia
State Energy Code for commercial buildings, and include submittal of proof of
compliance.

ONE AND TWO FAMILY DWELLING CODE

(International Residential Code for One and Two Family
Dwellings)

The CABO ONE AND TWO FAMILY DWELLING CODE (International
Residential Code for One and Two Family Dwellings), 2000 Edition, published by
the Southern Building Code Congress International, Inc., when used in
conjunction with these Georgia Amendments, shall constitute the official
Georgia State Minimum Standard One and Two Family Dwelling Code.

THESE AMENDMENTS ARE TO BE USED IN ADDITION TO THOSE
AMENDMENTS ADOPTED EFFECTIVE JANUARY 1, 2002. WHEN USED TOGETHER THEY
CONSTITUTE THE OFFICIAL GEORGIA STATE MINIMUM STANDARD ONE AND TWO FAMILY
DWELLING CODE.

Plumbing (Chapters 25 through 32) are deleted from the
CABO One and Two Family Dwelling Code according to Title 8,
Chapter 2, Article 1, Part of the Official Code of Georgia Annotated.

Electrical (Chapters 33 through 42) are deleted and
substitute for Electrical requirements the Georgia State Minimum Standard
ElectricalCode (National Electrical Code).

Appendices

Appendices are not enforceable unless they are specifically
referenced in the body of the code or adopted for enforcement in the ordinance
of the authority having jurisdiction.

GEORGIA STATE AMENDMENTS

CODE REFERENCE:

(a) Change all references from the ICC Electrical Code to the
Georgia State Minimum Standard National Electrical Code.

(b) Change all references from the International Energy
Conservation Code to the Georgia State Energy Code for Buildings. The Georgia
State Energy Code for Buildings shall be used for heating and air conditioning
equipment.

Scope

The provisions of the CABO One and Two Family Dwelling Code
(International Residential Code for One and Two Family Dwellings) shall apply
to the construction, alteration, movement, enlargement, replacement, repair,
equipment, use and occupancy, location, removal and demolition of detached one
and two family dwellings and multiple single family dwellings (townhouses) not
more than three stories in height with a separate means of egress and their
accessory structures.

GEORGIA STATE MINIMUM

REQUIREMENTS FOR BOILER/WATER HEATERS AND

PRESSURE VESSELS

(a) The State's Minimum Requirements for Boiler/Water Heaters
and Pressure Vessels, over 200,000 BTU (58.56 kW), 210 degrees Fahrenheit, or
120 gallons capacity, shall be established by O.C.G.A. Title 34, Chapter 11,
and the Rules and Regulations of the Georgia Department of Labor (Effective
January 1, 2002).

* Revise the CABO One and Two Family Dwelling Code
(International Residential Code for One and Two Family Dwellings), 2000
Edition, as follows:

CHAPTER 2

DEFINITIONS

* Revise Section R202 by adding the following
definition:

VALVE

Point of Delivery Service Shutoff. The point of
delivery for normal gas systems is the outlet of the service meter assembly or
the outlet of the service regulator or service shutoff valve where a meter is
not provided. Where a valve is provided at the outlet of the service meter
assembly, such valve shall be considered to be downstream of the point of
delivery. The point of delivery for undiluted liquefied petroleum gas systems
is the outlet of the first stage pressure regulator that provides utilization
pressure, exclusive of line gas regulators, in the system. (Effective January
1, 2003)

SECTION R703

EXTERIOR COVERING

* Add the following exceptions to Section R703.7:

R703.7 Stone and masonry veneer, general. All
stone and masonry veneer shall be installed in accordance with this chapter,
Table 703.4 and Figure R703.7. Such veneers installed over a backing of wood or
cold-formed steel shall be limited to the first story above grade and shall not
exceed 5 inches (127 mm) in thickness.

Exceptions:

3. For detached one and two family dwellings with a maximum
nominal thickness of 4 inches (102 mm) of exterior masonry veneer with a
backing of wood frame located in Seismic Design Category D1, the masonry veneer
shall not exceed 20 feet (6096 mm) in height above a noncombustible foundation,
with an additional 8 feet (2438 mm) permitted for gabled ends, or 30 feet (9144
mm) in height with an additional 8 feet (2438 mm) permitted for gabled ends
where the lower 10 feet (3048 mm) has a backing of concrete or masonry wall
provided the following criteria are met:

3.1 Braced wall panels shall be constructed with a minimum of
7/16 inch (11.1 mm) thick sheathing fastened with 8d common nails at 4 inches
(102 mm) on center on panel edges and at 12 inches (305 mm) on center on
intermediate supports.

3.2 The bracing of the top story shall be located at each end
and at least every 25 feet (7620 mm) on center but not less than 45% of the
braced wall line. The bracing of the first story shall be as provided in Table
R602.10.3.

3.3 Hold down connectors shall be provided at the ends of
braced walls for the second floor to first floor wall assembly with an
allowable design of 2100 lbs. (952 kg). Hold down connectors shall be provided
at the ends of each wall segment of the braced walls for the first floor to
foundation assembly with an allowable design of 3700 lbs. (1678 kg). In all
cases, the hold down connector force shall be transferred to the
foundation.

3.4 Cripple walls shall not be permitted.

4. For detached one and two-family dwellings with a maximum
actual thickness of 3 inches (76 mm) of exterior masonry veneer with a backing
of wood frame located in Seismic Design Category D2, the masonry veneer shall
not exceed 20 feet (6096 mm) in height above a noncombustible foundation, with
an additional 8 feet (2438 mm) permitted for gabled ends, or 30 feet (9144 mm)
in height with an additional 8 feet (2438 mm) permitted for gabled ends where
the lower 10 feet (3048 mm) has a backing of concrete or masonry wall, provided
the following criteria are met:

4.1 Braced wall panels shall be constructed with a minimum of
7/16 inch (11.1 mm) thick sheathing fastened with 8d common nails at 4 inches
(102 mm) on center on panel edges and at 12 inches (305 mm) on center on
intermediate supports.

4.2 The bracing of the top story shall be located at each end
and at least every 25 feet (7620 mm) on center but not less than 55% of the
braced wall line. The bracing of the first story shall be as provided in Table
R602.10.3.

4.3 Hold down connectors shall be provided at the ends of
braced walls for the second floor to first floor wall assembly with an
allowable design of 2300 lbs. (1043 kg). Hold down connectors shall be provided
at the ends of each wall segment of the braced walls for the first floor to
foundation assembly with an allowable design of 3900 lbs. (1769 kg). In all
cases, the hold down connector force shall be transferred to the
foundation.

4.4 Cripple walls shall not be permitted.

(Effective January 1, 2003)

* Revise Section R703.7.4.1.2 to read as follows:

R703.7.4.1.2 Seismic Design Categories D1
and D2. In Seismic Design Categories D1 and D2, provide single-wire
joint reinforcement, a minimum of No. 9 gage, at a spacing of 18 inches (457
mm) on center vertically. The joint reinforcement shall be continuous in the
veneer bed joint, with lap splices permitted between the veneer ties.

(Effective January 1, 2003)

CHAPTER 24

FUEL GAS

SECTION G2419 (409)

GAS SHUTOFF VALVES

* Add new Section G2419.2.1 to read as follows:

G2419.2.1 Point of Delivery Service Valve. Where
the point of delivery is the outlet of the service meter assembly, or the
outlet of the service regulator a service shutoff valve shall be installed.
Such valve is considered to be part of the customer piping system. (Effective
January 1, 2003)

GEORGIA STATE MINIMUM

STANDARD BUILDING CODE

(INTERNATIONAL BUILDING CODE)

The STANDARD BUILDING CODE (International Building Code),
2000 Edition, published by the Southern Building Code Congress International,
Inc., when used in conjuction with these Georgia Amendments, shall constitute
the official Georgia State Minimum Stnadard Building Code.

THESE AMENDMENTS ARE TO BE USED IN ADDITION TO THOSE
AMENDMENTS ADOPTED EFFECTIVE JANUARY 1, 2002. WHEN USED TOGETHER, THEY
CONSTITUTE THE OFFICIAL GEORGIA STATE MINIMUM STANDARD BUILDING CODE.

GEORGIA STATE AMENDMENTS

CODE REFERENCE:

(a) Change all references from the ICC Electrical Code to the
Georgia State Minimum Standard National Electrical Code respectively.

(b) Change all references from the International Energy
Conservation Code to the Georgia State Energy Code for Buildings. The Georgia
State Energy Code for Buildings shall be used for efficiency and coefficient of
ratings of equipment.

SCOPE:

The provisions of the Georgia State Minimum Standard Building
Code (International Building Code) shall apply to the construction, alteration,
movement, enlargement, replacement, repair, equipment, use and occupancy,
location, maintenance, removal and demolition of every building or structure of
any appurtenances connected or attached to such buildings or structures.

Exception: Detached one and two family dwellings
and multiple single-family dwellings (townhouses) not more than three stories
high with separate means of egress and their accessory structures shall comply
with the CABO One and Two Family Dwelling Code (International Residential
Code).

Appendices

Appendices are not enforceable unless they are specifically
referenced in the body of the code or adopted for enforcement in the ordinance
of the authority having jurisdiction.

* Revise the Standard Building Code (International
Building Code), 2000 Edition, as follows:

CHAPTER 23

WOOD

SECTION 2308

CONVENTIONAL LIGHT-FRAME CONSTRUCTION

* Revise Section 2308.11.2 to add the following
exceptions:

Section 2308.11.2 Concrete or masonry. Concrete
or masonry walls, or masonry veneer shall not extend above the basement.

Exceptions:

3. Masonry veneer is permitted to be used in the first two
stories above grade in Seismic Design Categories B or C provided the following
criteria are met:

3.1 "Type of Brace" per Section 2308.9.3 shall be Method 3
and the allowable shear capacity per Table 2306.4.1 shall be a minimum of 350
plf (5108 N/m) (ASD).

3.2 The bracing of the top story shall be located at each end
and at least every 25 feet (7620 mm) on center but not less than 40% of the
braced wall line. The bracing of the first story shall be located at each end
and at least every 25 feet (7620 mm) on center but not less than 35% of the
braced wall line.

3.3 Hold down connectors shall be provided at the ends of
braced walls for the second floor to first floor wall assembly with an
allowable design of 2000 lbs. (907.0 kg). Hold down connectors shall be
provided at the ends of each wall segment of the braced walls for the first
floor to foundation assembly with an allowable design of 3900 lbs. (1768 kg).
In all cases, the hold down connector force shall be transferred to the
foundation.

3.4 Cripple walls shall not be permitted.

(Effective January 1, 2003)

* Revise Section 2308.12.2 to add the following
exceptions:

Section 2308.12.2 Concrete or masonry. Concrete
or masonry walls, or masonry veneer shall not extend above the basement.

Exceptions: Masonry veneer is permitted to be
used in the first story above grade in Seismic Design Category D provided the
following criteria are met:

1. "Type of Brace" per Section 2308.9.3 shall be Method 3 and
the allowable shear capacity per Table 2306.4.1 shall be a minimum of 350 plf
(5108 N/m) (ASD).

2. The bracing of the first story shall be located at each
end and at least every 25 feet (7620 mm) on center but not less than 45% of the
braced wall line.

3. Hold down connectors shall be provided at the ends of
braced walls for the first floor to foundation assembly with an allowable
design of 2100 lbs. (952.5 kg).

4. Cripple walls shall not be permitted. (Effective January
1, 2003)

GEORGIA STATE MINIMUM

STANDARD PLUMBING CODE

(INTERNATIONAL PLUMBING CODE)

The STANDARD PLUMBING CODE (International Plumbing Code),
2000 Edition, published by the Southern Building Code Congress International,
Inc., when used in conjunction with these Georgia Amendments, shall constitute
the official Georgia State Minimum Standard Plumbing Code.

THESE AMENDMENTS ARE TO BE USED IN ADDITION TO THOSE
AMENDMENTS ADOPTED EFFECTIVE JANUARY 1, 2001 AND 2002. WHEN USED TOGETHER, THEY
CONSTITUTE THE OFFICIAL GEORGIA STATE MINIMUM STANDARD PLUMBING CODE.

Appendices

Appendices are not enforceable unless they are specifically
referenced in the body of the code or adopted for enforcement in the ordinance
of the authority having jurisdiction.

GEORGIA STATE AMENDMENTS

CODE REFERENCE:

(a) Change all references from the ICC Electrical Code to the
Georgia State Minimum Standard National Electrical Code respectively.

(b) The Georgia State Energy Code for Buildings shall be used
for efficiency and coefficient of ratings of plumbing equipment.

Scope:

The provisions of the Georgia State Minimum Standard Plumbing
Code shall apply to the erection, installation, alteration, replacement,
repairs, relocation, addition to, use or maintenance of plumbing systems within
the State of Georgia. The installation of fuel gas distribution piping and
equipment, fuel gas-fired water heaters, and water heater venting systems shall
be regulated by NFPA 54 (National Fuel Gas Code).

REQUIREMENTS FOR BOILER/WATER HEATERS AND PRESSURE
VESSELS

(a) The State's Minimum requirements for Boiler/Water Heaters
and Pressure Vessels over 200,000 BTU (58.56 kW), 210 degrees Fahrenheit, or
120 gallons capacity, shall be established by O.C.G.A Title 34, Chapter 11, and
the Rules and Regulations of the Georgia Department of Labor. (Effective
January 1, 2002)

* Revise the Standard Plumbing Code (International
Plumbing Code), 2000 Edition, as follows:

CHAPTER 3

GENERAL REGULATIONS

SECTION 304

RODENTPROOFING

* Revise Section 304.4 Openings for pipes to read as
follows:

304.4 Openings for Pipes. In or on structures
where openings have been made in walls, floors or ceilings for the passage of
pipes, such openings shall be sealed through the use of metal collars or other
approved methods.

(Effective January 1, 2003)

CHAPTER 4

FIXTURES, FAUCETS AND FITTINGS

SECTION 401

GENERAL

* Add new Section 401.4 to read as follows:

Section 401.4 Prohibited locations. No floor
drains or other plumbing fixtures except electric water heaters shall be
installed in a room containing air handling machinery when such room is used as
a plenum. Except deep-seal trap floor drains consisting of a minimum 4-inch
(102 mm) seal and supplied with a trap primer connected to a water distribution
pipe shall be permitted. When rooms are used as a plenum, equipment drains
shall be conveyed through an indirect waste receptor located outside such rooms
or other approved point of disposal.

(Effective January 1, 2003)

SECTION 403

MINIMUM PLUMBING FACILITIES

TABLE 403.1

MINIMUM NUMBER OF PLUMBING FACILITIES

* Revise Table 403.1 wording under Others category for
Residential Multiple family and One and Two Family Dwellings Occupancy and add
a new footnote g to read as follows:

(Effective January 1, 2003)

SECTION 410

DRINKING FOUNTAINS

* Revise Section 410.1 Approval to read as follows:

410.1 Approval. Drinking fountains shall conform
to ASME A112.19.1, ASME A112.19.2 or ASME A112.19.9, and water coolers shall
conform to ARI 1010. Where water is served in restaurants, drinking fountains
shall not be required.

(Effective January 1, 2003)

SECTION 419

URINALS

* Delete Section 419.3 Surrounding material and substitute to
read as follows:

419.3 Surrounding material. See Section 1209 of
the Building Code.

(Effective January 1, 2003)

CHAPTER 10

TRAPS, INTERCEPTORS AND SEPARATORS

SECTION 1003

INTERCEPTORS AND SEPARATORS

* Delete the current Georgia amendment to Section 1003 and
use Section 1003 of the 2000 Standard Plumbing Code as written.

(Effective January 1, 2003)

End of Amendments

GEORGIA STATE MINIMUM STANDARD GAS CODE

(International Fuel Gas Code)

The STANDARD GAS CODE (International Fuel Gas Code), 2000
Edition, published by the Southern Building Code Congress International, Inc.,
when used in conjunction with these Georgia Amendments, shall constitute the
official Georgia State Minimum Standard Gas Code.

THESE AMENDMENTS ARE TO BE USED IN ADDITION TO THOSE
AMENDMENTS ADOPTED EFFECTIVE JANUARY 1, 2001 AND 2002. WHEN USED TOGETHER, THEY
CONSTITUTE THE OFFICIAL GEORGIA STATE MINIMUM STANDARD GAS CODE.

Appendices

Appendices are not enforceable unless they are specifically
referenced in the body of the code or adopted for enforcement in the ordinance
of the authority having jurisdiction.

GEORGIA STATE AMENDMENTS

CODE REFERENCE:

(a) Change all references from the ICC Electrical Code to the
Georgia State Minimum Standard National Electrical Code.

(b) Change all reference from the International Energy
Conservation Code to the Georgia State Energy Code for Buildings. The Georgia
State Energy Code for Buildings shall be used for efficiency and coefficient of
performance rating of equipment.

SCOPE:

General. The provisions of the Georgia State
Minimum Standard Gas Code (International Fuel Gas Code) shall apply to the
installation of fuel gas piping systems, fuel gas utilization equipment, and
related accessories as follows:

1. Coverage of piping systems shall extend from the point of
delivery to the connections with gas utilization equipment. (See "point of
delivery").

2. Systems with an operating pressure of 125 psig (862 kPa
gauge) or less. Piping systems for gas-air mixtures within the flammable range
with an operating pressure of 10 psig (69 kPa gauge). LP-Gas piping systems
with an operating pressure of 20 psig (140 kPa gauge) or less.

3. Piping systems requirements shall include design,
materials, components, fabrication, assembly, installation, testing,
inspection, operation, and maintenance.

4. Requirements for gas utilization equipment and related
accessories shall include installation, combustion and ventilation air and
venting.

This Code shall apply to the following:

1. Portable LP-Gas equipment of all types that are not
connected to a fixed fuel piping system.

2. Installation of farm equipment such as brooders,
dehydrators, dryers, and irrigation equipment.

3. Raw material (feedstock) applications except for piping to
special atmosphere generators.

4. Oxygen-fuel gas cutting and welding systems.

5. Industrial gas applications using gases such as acetylene
and acetylene compounds, hydrogen, ammonia, carbon monoxide, oxygen, and
nitrogen.

6. Petroleum refineries, pipelines compressor or pumping
stations, loading terminals, compounding plants, refinery tank farms, and
natural gas processing plants.

7. Integrated chemical plants or portions of such plants
where flammable or combustible liquids or gases are produced by chemical
reactions or used in chemical reactions.

8. LP-Gas installations at utility gas plants.

9. Liquefied natural gas (LNG) installations.

10. Fuel gas piping in power and atomic energy plants.

11. Proprietary items of equipment, apparatus, or instruments
such as gas generating sets, compressors, and calorimeters.

12. LP-Gas equipment for vaporization, gas mixing, and gas
manufacturing.

13. Temporary LP-Gas piping for buildings under construction
or renovation that is not to become part of the permanent piping system.

14. Installation of LP-Gas systems for railroad switch
heating.

15. Installation of LP-Gas and compressed natural gas (CNG)
systems on vehicles.

16. Except as provided in Section 401.1.1 gas piping meters,
gas pressure regulators, and other appurtenances used by the serving gas
supplier in the distribution of gas, other than undiluted LP-Gas.

17. Building design and construction, except as specified
herein.

The requirements for the design, installation, maintenance,
alteration and inspection of mechanical systems operating with fuels other than
fuel gas shall be regulated by the Standard Mechanical Code (International
Mechanical Code).

* Revise the Standard Gas Code (International Fuel
Gas Code), 2000 Edition, as follows:

(a) The State's minimum requirements for natural gas systems
shall be established by the National Fuel Gas Code (NFPA 54). Areas not
specifically addressed by the NFPA 54 and which are addressed by the Georgia
State Minimum Standard Gas Code (International Fuel Gas Code), the Gas Code
shall be used as the supplement.

(b) The State's minimum requirements for Boilers/Water
Heaters and Pressure Vessels over 200,000 BTU (58.56 kW), 210 degrees
Fahrenheit or 120-gallon capacity shall be established by O.C.G.A. Title 34,
Chapter 11, and the Rules and Regulations of the Georgia Department of
Labor.

CHAPTER 2

DEFINITIONS

SECTION 202 (IFGC)

GENERAL DEFINITIONS

* Revise Section 202 GENERAL DEFINITIONS adding a new
definition to read as follows:

VALVE.

Point of Delivery Service Shutoff. The point of
delivery for natural gas systems is the outlet of the service meter assembly or
the outlet of the service regulator or service shutoff valve where a meter is
not provided. Where a valve is provided at the outlet of the service meter
assembly, such valve shall be considered to be downstream of the point of
delivery. The point of delivery for undiluted liquefied petroleum gas systems
is the outlet of the first stage pressure regulator that provides utilization
pressure, exclusive of line gas regulators, in the system.

(Effective January 1, 2003)

CHAPTER 4

GAS PIPING INSTALLATIONS

SECTION 409 (IFGC)

SHUTOFF VALVES

* Add new Section 409.2.1 to read as follows:

409.2.1 Point of Delivery Service Valve. Where
the point of delivery is the outlet of the service meter assembly or the outlet
of the service regulator, a service shutoff valve shall be installed. Such
valve is considered to be part of the customer piping system.

(Effective January 1, 2003)

End of Amendments.

Errata to the January 1, 2002 Georgia Amendments to the
2000 Standard Building Code/International Building Code

Update your copy of the January 1, 2002 Georgia Amendments to
the 2000 Standard Building Code/International Building Code, by making the
following correction(s).

CHAPTER 16

STRUCTURAL DESIGN

SECTION 1609

WIND LOADS

1609.2 Definitions. BUILDING, SIMPLE DIAPHRAGM

Change Note 8 "form" to "from".

CHAPTER 17

STRUCTURAL TESTS AND SPECIAL INSPECTIONS

SECTION 1705

QUALITY ASSURANCE FOR SEISMIC RESISTANCE.

1705.1 Scope.

Change "See Section 1612 and 1615 of said code" to 1613 and
1621.

CHAPTER 18

SOILS AND FOUNDATIONS

SECTION 1802

FOUNDATION AND SOILS INVESTIGATIONS

1802.2 General.

Change 1802.2 to 1802.1 and "General" to "Where
required".

End of Errata

Errata to the January 1, 2002 Georgia Amendments to the
2000 CABO 1 and 2 Family Dwelling Code/International Residential
Code

Update your copy of the January 1, 2002 Georgia Amendments to
the CABO 1 and 2 Family Dwelling Code/International Residental Code, 2000
Edition, by making the following correction(s).

CHAPTER 3

BUILDING PLANNING

SECTION R317

SMOKE ALARMS

R317.1 Smoke detectors required.

Change next to last sentence to: All detectors shall be
interconnected such that the actuation of one alarm will actuate all the alarms
in the individual unit and shall provide an alarm which is audible in all
sleeping areas.

CHAPTER 5

FLOORS

SECTION R502

WOOD FLOOR FRAMING

R502.2.1 Decks.

Change R505.2.1.1, R505.2.1.2 to R502.2.1.1 and
R502.2.1.2.

CHAPTER 24

FUEL GAS

SECTION G2409 (308)

CLEARANCE REDUCTION

G2409 (308) Clearance Reduction.

Change Section G2409 (308) Clearance Reduction to Section
G2408 (305) Installation.

G2409.2 Reduction Table. Change G2409.2
Reduction table to G2408.2 (305.2) Elevation of ignition source.

End of Errata
Source: Legislative text reproduced verbatim
Plain English

Ga. Comp. R. & Regs. ch. 110-11-1 § 110-11-1-.12, adopted effective January 1, 2003, establishes the suite of Georgia State Minimum Standard Codes for construction, covering electrical, energy conservation, one- and two-family dwellings, building, plumbing, and gas systems. Each code is formed by pairing a nationally recognized model code edition with Georgia-specific amendments, and the Georgia amendments take precedence wherever conflicts exist. The rule also includes errata corrections to previously adopted amendments and sets climate-zone-specific energy compliance pathways for residential buildings across Georgia.

Written by anthropic/claude-sonnet-4.6 · Reviewed on October 27, 2026

Plain English — not legal advice.

For Property Managers

Property owners and managers overseeing new construction, renovation, or systems replacement in Georgia should be aware that § 110-11-1-.12 sets the baseline technical standards for electrical, energy, structural, plumbing, and gas work on residential and commercial properties. Compliant operators ensure that contractors and designers reference the correct code edition paired with the applicable Georgia amendments—not the model code alone—and that permit applications reflect the chosen compliance pathway (such as a climate-zone Single-Step package or a trade-off worksheet). Operators also confirm that installed fenestration products carry required U-factor and SHGC labels and that ground-fault circuit-interrupter protection is provided in all locations specified under the Georgia-amended Article 210.8.

General guidance for property managers — not legal advice for your specific situation. Consult an attorney for advice on your case.

For Tenants

Tenants living in or moving into Georgia residential properties benefit from § 110-11-1-.12 because it sets minimum construction and systems standards—including insulation levels, window energy performance, electrical safety protections such as GFCI outlets in bathrooms and kitchens, and gas shutoff valve requirements—that apply to the dwelling's construction or renovation. If a tenant believes a unit was built or altered without meeting these minimum standards, they may raise the issue with the local building or code enforcement office, which is the authority having jurisdiction under this rule. Tenant-rights organizations and legal aid resources can help identify whether a code concern is relevant to habitability or lease obligations under Georgia law.

General guidance for tenants — not legal advice for your specific situation. Consult a tenant-rights organization or attorney for advice on your case.

Generated October 27, 2026 — auto-generated, not yet human-reviewed. See /transparency for methodology.

Effective Timeline

Current
Oct 27, 2026
Click on timeline segments to view historical versions.

References Out

No outbound references recorded yet for this provision.

References In

No inbound references recorded yet for this provision.

Related Rules

§ 244.260
Compliance required
§ 14.567
ADOPTED BY REFERENCE
§ 244.340
Sewer and water connections

Source Information

Snapshot SHA:
Fetched:Oct 27, 2026, 10:01 PM UTC